Trouble

 

Probable Cause

 

Remedy

ERRATIC CYCLING OF

C.

Liquid level sensing probe

C.

Correct liquid level sensing probe

CARBONATOR (con’t).

 

wired wrong.

 

wiring.

 

D.

Dirty or oily liquid level sensing

D.

Clean liquid level sensing probe.

 

 

probe.

 

 

WATER PUMP MOTOR

A. Water inlet supply line shutoff

OPERATES BUT WATER

valve closed.

PUMP DOES NOT PUMP

 

WATER.

 

A.Open water inlet supply line shutoff valve.

B.Kinked water inlet supply line.

C.Restriction between water pump outlet and carbonator tank inlet.

D.Foreign object in water pump bypass.

B.Straighten water inlet supply line.

C.Remove restriction.

D.Clean bypass. (Note: Count number of turns bypass screw makes when removing and install same number of turns).

 

E. Water pump worn out.

E.

Replace water pump.

WATER PUMP CAPACITY

A.

Water supply capacity too low.

A.

Water inlet supply must be at a

TOO LOW.

 

 

 

minimum of 300-gallons per hour

 

 

 

 

with a maximum water pressure

 

 

 

 

of 80-psi.

 

B.

Water filter clogged.

B.

Replace water filter cartridge as

 

 

 

 

instructed.

 

C.

Inoperative water pump.

C.

Replace water pump.

 

 

 

TROUBLESHOOTING REFRIGERATION SYSTEM

 

 

 

 

 

 

 

COMPRESSOR DOES NOT

A.

Ice bank sufficient.

A.

Refrigeration not called for.

OPERATE.

 

 

 

 

 

B.

REFRIGERATION POWER

B.

Place REFRIGERATION POWER

 

 

switch in ‘OFF’position.

 

switch in ‘ON’position.

 

C. Electrical power to Cooling

C. Turn on electrical power to

 

 

Unit turned off.

 

Cooling Unit.

D.No Cooling Unit power source. D. Replace fuse or reset circuit

 

Blown fuse or tripped circuit

 

breaker.

 

breaker.

 

 

E.

Loose, disconnected, or

E.

Tighten connections or replace

 

broken wiring.

 

broken wiring.

F.

Hi-pressure cutout switch

F.

Reset pressure switch (see

 

tripped.

 

REFRIGERATION SYSTEM

 

 

 

TEMPERATURE SENSING

 

 

 

DEVICE AND HIGH-PRESSURE

 

 

 

CUTOUT SWITCH in

 

 

 

OPERATORS INSTRUCTIONS

 

 

 

SECTION.

G.

Low Voltage.

G.

Voltage must be at least 208 volts

 

 

 

at compressor terminals when

 

 

 

compressor is trying to start.

H. Inoperable run capacitor, start

H.

Replace inoperable part.

 

capacitor, or relay.

 

 

I.

Inoperable compressor.

I.

Replace compressor.

33

300614000

Page 37
Image 37
Cornelius 000 PLUS Water Pump Motor, Operates but Water, Pump does not Pump Water, Water Pump Capacity, Too Low, Section

000 PLUS, 10 specifications

Cornelius 10,000 PLUS is a pioneering innovation in the beverage dispensing industry, designed to cater to the evolving needs of commercial establishments. This advanced system combines state-of-the-art technology with user-friendly features, making it a standout choice for restaurants, cafes, and bars aiming to enhance their beverage service.

One of the main features of the Cornelius 10,000 PLUS is its impressive capacity. With the ability to dispense a wide variety of beverages, including soft drinks, cocktails, and craft beers, the system supports a large volume of service, perfect for high-demand environments. The modular design allows for easy expansion, enabling businesses to add additional flavors or beverages as needed without major overhauls.

The technology behind the Cornelius 10,000 PLUS is equally impressive. It utilizes advanced cooling technology to ensure that beverages are served at the optimal temperature, enhancing the customer experience. The integrated touchless dispensing mechanism minimizes waste and ensures a hygienic experience, addressing growing concerns about cleanliness in food service environments. This technology also improves speed, allowing staff to serve customers more efficiently.

Another key characteristic of the Cornelius 10,000 PLUS is its digital integration capabilities. The system can be connected to a central management platform that tracks sales, inventory levels, and maintenance needs in real-time. This allows operators to optimize their beverage offerings based on customer preferences and reduces downtime through proactive maintenance alerts.

In addition to its performance features, the Cornelius 10,000 PLUS is designed with sustainability in mind. The system employs energy-efficient practices, reducing its environmental footprint while lowering operational costs. The materials used in construction are durable yet eco-friendly, ensuring longevity and less waste.

Overall, the Cornelius 10,000 PLUS stands out as an essential tool for any business looking to elevate its beverage service. With its combination of high capacity, cutting-edge technology, and sustainability features, it not only meets the demands of today’s fast-paced service environments but also positions establishments for future growth and success.