Crestron Commercial Lighting Design Guide

Green Light Power Switching

Feed Type: Choose one of the following to specify the type of feed:

MLO

Main lug only

MCB60

60A back-fed main circuit breaker

MCB80

80A back-fed main circuit breaker

MCB100

100A back-fed main circuit breaker

MCB125

125A back-fed main circuit breaker

(available for 277V only)

Note: Main feeds are 3-phase, 4-wire; rated 225A @ 120/208V or250A @ 277/480V. Consult Crestron Sales Support Services for 400Afeed and other main circuit breaker options.

Number of Circuits: choose one of the following numeric values from the appropriate column to specify the number of controlled circuits in the panel:

 

GLPS-HSW-MLO

GLPS-HSW-MCB

Small:

8, 12

8, 12

Medium:

16, 20, 24, 28, 30

16, 20, 24, 27, 30

Large:

32

32

Extra Large:

36, 40, 42

36, 39

Note: Small,” “Medium,” “Large and Extra Largerefer to the default panel size per number of circuits. Consult Crestron Sales Support Services for alternate configurations.

Voltage: To specify the circuit breaker voltage, enter 120for 120/208V or 277for 277/480V.

AIC Rating: Choose one of the following values from the appropriate column to specify the Ampere Interrupting Capacity of the circuit breakers:

120 Volt

277 Volt

10K

18K

22K

35K

65K

65K

Note: Consult Crestron Sales Support MCB options.

Door OptionEnter NDto omit the local control access door. (The circuit breaker door cannot be omitted).

Doc 4775A

15

Page 19
Image 19