Crestron Commercial Lighting Design Guide | Green Light Power Switching |
Feed Type: Choose one of the following to specify the type of feed:
MLO | Main lug only |
MCB60 | 60A |
MCB80 | 80A |
MCB100 | 100A |
MCB125 | 125A |
(available for 277V only)
Note: Main feeds are
Number of Circuits: choose one of the following numeric values from the appropriate column to specify the number of controlled circuits in the panel:
| ||
Small: | 8, 12 | 8, 12 |
Medium: | 16, 20, 24, 28, 30 | 16, 20, 24, 27, 30 |
Large: | 32 | 32 |
Extra Large: | 36, 40, 42 | 36, 39 |
Note: “Small,” “Medium,” “Large and “Extra Large” refer to the default panel size per number of circuits. Consult Crestron Sales Support Services for alternate configurations.
Voltage: To specify the circuit breaker voltage, enter “120” for 120/208V or “277” for 277/480V.
AIC Rating: Choose one of the following values from the appropriate column to specify the Ampere Interrupting Capacity of the circuit breakers:
120 Volt | 277 Volt |
10K | 18K |
22K | 35K |
65K | 65K |
Note: Consult Crestron Sales Support MCB options.
Door
Doc 4775A | 15 |