Crestron electronic GLPS-HSW-FT Crestron Commercial Lighting Design Guide, GLPS-HDSW-FT Continued

Models: GLPS-HSW-FT GLPS-HDSW-FT GLPS-HSW GLPS-SW-FT GLPS-SW IPAC-GL1

1 108
Download 108 pages 57.08 Kb
Page 29
Image 29
GLPS-HDSW-FT (Continued)

Crestron Commercial Lighting Design Guide

Green Light Power Switching

GLPS-HDSW-FT (Continued)

SPECIFICATIONS

Load Ratings

Switch Channels: 8 to 56 single-pole, 4-28 double-pole, depending upon panel size and relay combinations, each channel phase-independent

Maximum per Channel: 20 Amps @ 100 to 347 Volts AC, 50/60 Hz; 1/2 HP @ 120 Volts, 1-1/2 HP @ 277 Volts Switched Load Types: Incandescent, Magnetic Low-Voltage, Electronic Low-Voltage, Neon/Cold Cathode, Fluorescent Lamp Ballast, High-Intensity Discharge, Motors

Dimmed Load Types (special order): 0-10 Volt 4-Wire Dimmable Fluorescent Ballast

Rated Relay Lifetime: 30,000 cycles at full rated electronic ballast load

Input Power

Line Power: 120, 277, or 347 VAC, 20 Amps maximum per circuit, 50/60 Hz

Cresnet Power Usage: 50 Watts (2.08 Amps @ 24 Volts DC) per panel, use Crestron GLA-PWS50 or equivalent power supply

Lightning Protection

Can withstand 6 kV / 3 kA surge, as per IEC 61000-4-5 and ANSI/IEEE C62.41-1991

Enclosure

NEMA Type 1, IP20 rated protection, for indoor use only Back Box: 16 Gauge galvanized steel, flush or surface wall mount

Front Cover: 16 Gauge steel, grey powder coat finish

Environmental

Temperature: 32° to 104°F (0° to 40°C)

Humidity: 10% to 90% RH (non-condensing)

Dimensions

Small: 23-1/2 x 14-3/8 x 4 in (59.7 x 36.5 x 10.2 cm) HWD

Large: 38-1/4 x 14-3/8 x 4 in (97.2 x 36.5 x 10.2 cm) HWD

Doc 4775A

25

Page 29
Image 29