Crestron electronic IPAC-GL1, GLPS-SW CAEN Installation, CAEN Enclosure Framing, CAEN 4X2 Framing

Models: GLPS-HSW-FT GLPS-HDSW-FT GLPS-HSW GLPS-SW-FT GLPS-SW IPAC-GL1

1 108
Download 108 pages 57.08 Kb
Page 42
Image 42
CAEN Installation

CAEN Enclosures

Crestron Commercial Lighting Design Guide

CAEN Installation

In accordance with all national and local codes a licensed electrician must mount the enclosure. Special attention must be made to NEC Article 110.26(A)(2) concerning minimum work space requirements.

When choosing components to place in CAEN enclosures, refer to the table on the previous page to ensure that the maximum weight capacity is not exceeded. The weight of each module is listed on the product page on the Crestron website.

CAUTION: These enclosures house equipment that requires air cooling. Therefore, mount in a well-ventilated area. The ambient temperature range should be 32°F

to 104°F (0°C to 40°C). The relative humidity should range from 0% to 90% (non-condensing). Furthermore,

CAEN Enclosure Framing

CAEN enclosures 2X1, 4X1, and 7X1 fit between standard wall stud spacing (16 inches on center).

CAEN 2X1, 4X1, and 7X1 Framing

allow adequate clearance in front of the vented cover for servicing and ventilation.

NOTES: Unless otherwise indicated, the lighting system specified in this guide is modular, requiring assembly in the field by a licensed electrician in accordance with all national and local codes. If you require a UL listed panel, Crestron offers this service through its UL listed panel shop. This includes complete in-factory system configuration and assembly by Crestron for an additional fee. All commercial lighting systems include factory assembled, UL listed panels.

Install modules into the lowest available spaces and continue toward the top of the enclosure.

Enclosures are intended for indoor use only.

When flush mounting, 5/8” drywall is preferred.

CAEN enclosures 4X2 and 7x2 require framing modification. The weight of the enclosure rests on a sill plate, and does not distort the surrounding wallboard.