SECTION VI - BURNER SPECIFICATIONS

NOTICE

Series 24 boiler ratings and capacities are based upon the following burners, pump pressures, noz z le siz es and manifold pressures. Refer to instructions furnished with burner for additional information regarding proper installation, fuel piping, wiring details, burner adjustments, service instructions and burner start-up.

Table VI: Beckett Burner Specifications

OIL BURNERS

 

BURNER

 

 

 

 

BURNER SETTINGS

 

PUMP PRESS.

 

NOZZLE DATA

BOILER

BURNER

BURNER

AIR TUBE

 

 

 

(PSI)

NOZZLE

 

 

 

 

 

 

 

INPUT

 

 

 

 

 

 

 

 

 

MODEL

MFR.

MODEL

COMB.

 

 

 

 

 

 

 

 

MAKE

 

(GPH)

HEAD

AIR

AIR

AIR DAMPER

LOW

 

HIGH

GPH X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHUTTER

BAND

LOW

HIGH

FIRE

 

FIRE

 

ANGLE-TYPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-03

3.1

BECKETT

CF-500

CF60KK

2

10

3

N/A

N/A

---

 

150

HAGO

2.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-04

4.2

BECKETT

CF-800

CF80KH

1

8

0

N/A

N/A

---

 

150

HAGO

3.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-05

5.6

BECKETT

CF-800

CF80KH

2

10

6

N/A

N/A

---

 

150

HAGO

4.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-06

7.0

BECKETT

CF-1400

CF66KD

3

N/A

N/A

2.75

4.0

150

 

300

HAGO

4.00 X 60° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-07

8.3

BECKETT

CF-1400

CF66KD

4

N/A

N/A

3.0

6.5

150

 

275

HAGO

5.00 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-08

9.6

BECKETT

CF-1400

CF66KEE

1

N/A

N/A

3.5

8.5

150

 

300

HAGO

5.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-09

11.6

BECKETT

CF-2300A

CF66KG

0

N/A

N/A

2.0

4.0

150

 

275

HAGO

7.00 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-10

13.2

BECKETT

CF-2300A

CF66KG

1

N/A

N/A

2.0

6.0

150

 

275

HAGO

8.00 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-11

14.8

BECKETT

CF-2500

CF66KP

0

N/A

N/A

0.5

3.0

275

 

275

HAGO

(L) 4.50 X 45° - P

 

 

(H) 4.50 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24-12

16.4

BECKETT

CF-2500

CF66KP

0

N/A

N/A

0.5

4.0

275

 

275

HAGO

(L) 5.00 X 45° - P

 

 

(H) 5.00 X 45° - P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS BURNERS (Natural Gas)

Boiler

Gas

 

Damper Settings

 

Manifold Pressure ("WC)

Rate

 

Minimum Inlet Pressure "WC1

 

Burner

 

High

 

 

Low Fire

 

 

 

By Gas Train Pipe Size

 

Model

Low Fire

Shutter

Band

High Fire

Control

 

 

 

Model

Fire

(Start)

 

 

 

 

 

 

 

1"

 

1 1/4"

1 1/2"

2"

 

2 1/2"

 

 

 

 

 

 

 

 

24-03

CG10.1S

 

 

10

1

(1.3)

2.5

On/Off

3.24

 

3.13

--

--

 

--

24-04

CG10.4S

 

 

5

2

(1.3)

2.6

On/Off

3.64

 

3.4

--

--

 

--

24-05

CG10.5S

 

 

7

1

(1)

3.3

On/Off

4.61

 

4.26

--

--

 

--

24-06

CG10.6S

 

 

10

6

(1.1)

3.64

On/Off

5.43

 

4.76

4.38

--

 

--

24-07

CG15.3S

18

43

 

 

0.9

3.1

Lo/Hi/Lo

5.31

 

4.44

3.99

--

 

--

24-08

CG15.4S

21

63

 

 

0.95

3.3

Lo/Hi/Lo

6.14

 

4.9

4.41

--

 

--

24-09

CG25.2S

23

47

 

 

0.8

3.43

Lo/Hi/Lo

--

 

4.69

4.28

3.86

 

--

24-10

CG25.3S

26

52

 

 

0.8

3.44

Lo/Hi/Lo

--

 

--

4.94

4.4

 

3.98

24-11

CG25.4S

28

58

 

 

0.8

3.0

Lo/Hi/Lo

--

 

--

4.88

4.21

 

3.68

24-12

CG50.2S

10

25

 

 

0.8

2.1

Lo/Hi/Lo

--

 

--

3.87

3.56

 

2.94

1. Standard burners are indicated with bold numbering in shaded boxes. The other burners shown are optional.

57

Page 57