Recommendation 1 — Use when:

system return water is not less than 135° F for prolonged periods of time

system flow does not impact flow through the boiler

Pipe Sizing and Notes

 

SUPPLY

 

RETURN PIPING SIZE (IN)

 

 

 

 

 

 

 

 

PIPING

 

 

RETURN

RETURN

 

 

SIZE (IN)

 

 

HEADER

BRANCH

 

 

 

(1)

RETURN (2)

(2A)

(QTY.) SIZE (2B)

 

 

20°F

 

40°F

20°F

40°F

20°F

20°F

 

MODEL

DROP

DROP

DROP

DROP

DROP

DROP

 

24-03

2

 

1-1/2

2

1-1/2

NOTES:

24-04

2

 

1-1/2

2

1-1/2

24-05

2

 

1-1/2

2

1-1/2

1.All piping is schedule 40.

24-06

2-1/2

 

1-1/2

2-1/2

1-1/2

2.Pipe sizes listed are based on a 20°F or 40°F differential (temperature drop).

24-07

2-1/2

 

2

2-1/2

2

Select one to match application.

24-08

2-1/2

 

2

2-1/2

2

3.When specified return piping size is less than 3”, install 3” X 12” nipple and appropriate

24-09

3

 

2

3

2

size bell reducer directly into boiler return tapping as shown.

24-10

3

 

2-1/2

3

2-1/2

4.Drain valve — ball valve preferable, gate valve acceptable alternative

24-11

3

 

2-1/2

3

2-1/2

(supplied by others).

24-12

4

 

2-1/2

4

2-1/2

3

(2) 3

- Minimum valve size per ASME code is 3/4” NPT.

Figure 31: Series 24 Minimum Piping Recommendation 1 - Water Boiler