Table 13. Electrical Output

 

120V Models

208V Models

230V Models

 

 

 

 

Power Levels

 

2700W

 

(rated at nominal inputs)

 

 

 

 

 

 

 

Regulation (Normal mode)

 

-6% to +6% of nominal voltage

 

 

NOTE: This varies based on auto-detected input voltage or customer settings.

 

 

 

 

Regulation (Battery mode),

 

-6% to +6% of nominal voltage

 

Nominal Voltage ±5%

NOTE: This varies based on auto-detected input voltage or customer settings.

 

 

 

 

 

Voltage Waveform

 

Sine wave

 

 

 

 

 

Output Receptacles

(1) L5-20R, 20A

(1) L6-20R, 20A

(6) IEC 320-C13, 10A

 

(2) 5-20R, 20A

(2) L6-30R, 30A

(1) IEC 320-C19, 16A

 

(2) IEC 320-C13, 15A

 

(2) IEC 320-C13, 10A

 

 

 

Table 14. Environmental and Safety

 

 

 

 

 

 

 

120V Models

208V Models

230V Models

 

 

Operating Temperature

Up to 1,500 meters: 0°C to 40°C (32°F to 104°F)

 

Above 1,500 meters: 0°C to 35°C (32°F to 95°F)

 

 

 

 

Transit/Storage

 

-15°C to 60°C (5°F to 140°F)

 

Temperature

 

 

 

 

 

 

 

Relative Humidity

 

0–95% noncondensing

 

 

 

Operating Altitude

Up to 3,048 meters (0–10,000 ft) above sea level

 

 

Audible Noise

Less than 55 dBA on line/bypass mode (less than 75% load), room temperature

 

 

Fan Speed

Low speed: when the load is < 80%

 

High speed: when the load is >80% or the UPS is in Battery mode

 

 

Surge Suppression

ANSI/IEEE C62.41; 2002 Category B

 

 

 

Safety Conformance

UL 1778 4th Edition;

UL 1778 4th Edition;

 

CSA C22.2, No. 107.3

CSA C22.2, No. 107.3;

 

 

 

IEC/EN 62040-1-1;

 

 

 

IEC/EN 60950-1

 

 

 

 

Agency Markings

UL, cUL, NOM/NYCE

UL, cUL

UL, cUL, CE, GS, GOST,

 

 

 

BSMI, S-MARK, KC,

 

 

 

CQC, NRCS, SIRIM

 

 

 

 

EMC (Class A)

FCC, ICES-003

FCC, ICES-003, VCCI

CE, BSMI, CQC, C-tick

 

 

 

 