Table 7. Settings (continued)
Description | Available Settings | Default Setting | |
|
|
|
|
Reset Peak Headroom Watts | [No] [Yes] |
| No |
| If No, no action. |
| |
| If Yes, the Peak Headroom Watts value is cleared |
| |
| and the date and time stamp for this statistic is set |
| |
| to the current date and time. |
| |
|
|
|
|
Clear Event Log | The number after “Total events” shows how | — | |
|
| ||
| many events are currently stored in the log. |
| |
| Press the | button for one second to reset |
|
| the event count to zero and clear the log. |
| |
|
|
| |
LCD Contrast | [+0] | ||
| [+4], [+5] |
|
|
The LCD Contrast is adjustable and the valid range is from
Transferring the UPS Between Modes
Transferring between modes includes:
STransferring from Normal to Bypass mode
STransferring from Bypass to Normal mode
Transferring from Normal to Bypass Mode
To transfer from Normal to Bypass mode:
1Press the button for one second to go to the main menu selection and scroll down to the Control menu using the button.
2Press the button to enter the Control menu.
3Select Go to Bypass.
The text on the screen changes to Manual Bypass Command Sent. The Bypass mode icon flashes, indicating Bypass mode.
46 Operation