[2].......... AC Failure

P r o g r a m D e s c r i p t i o n s : 5 . 1 1 P G M O u t p u t O p t i o n s

NOTE: For the 2-wire smoke option to work, connector JP1 must be removed from the PC1555MX control board.

NOTE: 2-Wire smoke detectors use PGM2 as a supervised input with a 2200end-of-line resistor. A trouble condition will be generated if an open condition is detected between PGM2 and Aux+ .

NOTE: For option [04], 2-wire smoke, do not change the PGM Output Attributes from the default settings.

[05] Armed Status

When the system is armed, the PGM output will activate at the beginning of the exit delay. The output deactivates when the system is disarmed.

[06] Ready To Arm

The PGM will be active as long as the system is ready to arm and all non-force armable zones on the system are restored. Once an access code is entered to arm the system and the exit delay begins, the PGM output is deactivated.

[07] Keypad Buzzer Follower Mode

The PGM will activate when any of the following events occur and will remain active for as long as the keypad buzzer is active:

• Door Chime

• Entry Delay

Auto-Arm Prealert

• Audible Exit Delay

• 24 Hour Supervisory Buzzer Zone

[08] Courtesy Pulse

Upon arming, the PGM output will activate for the duration of the exit delay plus an additional two minutes. Upon disarming, the PGM output will activate for the duration of the entry delay plus an additional two minutes.

[09] System Trouble Output

The PGM output will activate when any of the selected trouble conditions are present. It will deactivate when all the selected trouble conditions are cleared.

The PGM attributes for this option, programmed in Sections

[141]to [154], differ from the standard selection of attributes. Program which trouble conditions will activate the output by selecting some or all of the following attributes:

Attribute

[1].......... Service Required (battery, bell, general trouble, general tamper, general supervisory)

[2].......... AC Failure

[3].......... Telephone Line Trouble

[4].......... Failure to Communicate

[5].......... Fire Trouble / Zone Fault

[6].......... Zone Tamper

[7].......... Zone Low Battery

[8].......... Loss of Clock

[10]System Event (Strobe Output)

The output activates when any of the selected system events (alarms) occur on the system.

NOTE: This output will activate for silent and audible alarms or medical conditions only. It will not activate during pre-alert or delays.

If attribute [8] is turned ON, the output will activate for the number of seconds programmed in the PGM output timer (section [164]).

If attribute [8] is turned OFF, in the armed state, the output will deactivate only once the system is disarmed. If an alarm acti- vates this output in the disarmed state, the output will deacti- vate if a user enters a valid access code while the Bell Cut-off

timer is counting down. The output will also deactivate if someone arms the system after the Bell Cut-off has expired. This output can be used to indicate that an alarm has occurred before entering the premises.

The PGM attributes for this option, programmed in Sections

[141]to [154], differ from the standard selection of attributes. Program which events will activate the output by selecting some or all of the following attributes:

Attribute

[1].........Burglary (Delay, Instant, Interior, Stay/Away and 24 Hour Burglary Zones)

[2].........Fire (Fire Keys, Fire Zones)

[3].........Panic (Panic Keys and Panic Zones)

[4].........Medical (Auxiliary Keys, Medical and Emergency Zones)

[5].........Supervisory (Supervisory, Freezer and Water Zones)

[6].........Priority (Gas, Heat, Sprinkler and 24 Hour Latch- ing Zones)

[7].........Holdup (Holdup zones)

[8].........Output Follows Timer (output will activate for the number of seconds programmed in the PGM Out- put Timer) / Output Latched

NOTE: If attribute [8] is turned ON, attributes [1-7] must also be turned ON.

PGM Output Timer . . . . . . . . . . . . . . . . . . . . . . . Section [164]

[11] System Tamper (All Sources)

The PGM output will activate when any tamper condition is present and will deactivate when all tampers are restored.

[12] TLM and Alarm

The PGM output activates when the system experiences both a telephone line trouble and an alarm. When the system is armed, the output will deactivate only if an access code is entered or if the telephone line is restored.

If an alarm activates this output in the disarmed state, the out- put will deactivate if a user enters a valid access code while the Bell Cut-off timer is counting down, or if the telephone line is restored. The output will also deactivate if someone arms the system after the Bell Cut-off has expired.

NOTE: This output will activate for all silent and audible alarms except the Duress alarm and 24-hr PGM inputs.

[13] Kissoff Output

The output will activate for two seconds after the control panel receives the kissoff transmission from the central station.

[14] Ground Start Pulse

The PGM Output will activate for two seconds to obtain a dial tone on Ground Start telephone equipment before the panel attempts to dial. Insert two 2-second pauses at the beginning of the telephone number when using this option.

[15] Remote Operation (DLS-1 Support)

This output can be activated and deactivated remotely using the DLS software.

[16] LINKS1000 Support (PGM1 Only)

The PGM output will be used as a data wire to communicate telephone number information for the LINKS1000 cellular unit.

[17] Away Armed Status

When the system is armed in the Away mode, the PGM output will activate at the beginning of the exit delay. The output deactivates when the panel is disarmed.

WWW.DIYALARMFORUM.COM