P r o g r a m D e s c r i p t i o n s : 5 . 1 1 P G M O u t p u t O p t i o n s
NOTE: For the
NOTE:
NOTE: For option [04],
[05] Armed Status
When the system is armed, the PGM output will activate at the beginning of the exit delay. The output deactivates when the system is disarmed.
[06] Ready To Arm
The PGM will be active as long as the system is ready to arm and all
[07] Keypad Buzzer Follower Mode
The PGM will activate when any of the following events occur and will remain active for as long as the keypad buzzer is active:
• Door Chime | • Entry Delay |
• | • Audible Exit Delay |
• 24 Hour Supervisory Buzzer Zone
[08] Courtesy Pulse
Upon arming, the PGM output will activate for the duration of the exit delay plus an additional two minutes. Upon disarming, the PGM output will activate for the duration of the entry delay plus an additional two minutes.
[09] System Trouble Output
The PGM output will activate when any of the selected trouble conditions are present. It will deactivate when all the selected trouble conditions are cleared.
The PGM attributes for this option, programmed in Sections
[141]to [154], differ from the standard selection of attributes. Program which trouble conditions will activate the output by selecting some or all of the following attributes:
Attribute
[1].......... Service Required (battery, bell, general trouble, general tamper, general supervisory)
[2].......... AC Failure
[3].......... Telephone Line Trouble
[4].......... Failure to Communicate
[5].......... Fire Trouble / Zone Fault
[6].......... Zone Tamper
[7].......... Zone Low Battery
[8].......... Loss of Clock
[10]System Event (Strobe Output)
The output activates when any of the selected system events (alarms) occur on the system.
NOTE: This output will activate for silent and audible alarms or medical conditions only. It will not activate during
If attribute [8] is turned ON, the output will activate for the number of seconds programmed in the PGM output timer (section [164]).
If attribute [8] is turned OFF, in the armed state, the output will deactivate only once the system is disarmed. If an alarm acti- vates this output in the disarmed state, the output will deacti- vate if a user enters a valid access code while the Bell
timer is counting down. The output will also deactivate if someone arms the system after the Bell
The PGM attributes for this option, programmed in Sections
[141]to [154], differ from the standard selection of attributes. Program which events will activate the output by selecting some or all of the following attributes:
Attribute
[1].........Burglary (Delay, Instant, Interior, Stay/Away and 24 Hour Burglary Zones)
[2].........Fire (Fire Keys, Fire Zones)
[3].........Panic (Panic Keys and Panic Zones)
[4].........Medical (Auxiliary Keys, Medical and Emergency Zones)
[5].........Supervisory (Supervisory, Freezer and Water Zones)
[6].........Priority (Gas, Heat, Sprinkler and 24 Hour Latch- ing Zones)
[7].........Holdup (Holdup zones)
[8].........Output Follows Timer (output will activate for the number of seconds programmed in the PGM Out- put Timer) / Output Latched
NOTE: If attribute [8] is turned ON, attributes
PGM Output Timer . . . . . . . . . . . . . . . . . . . . . . . Section [164]
[11] System Tamper (All Sources)
The PGM output will activate when any tamper condition is present and will deactivate when all tampers are restored.
[12] TLM and Alarm
The PGM output activates when the system experiences both a telephone line trouble and an alarm. When the system is armed, the output will deactivate only if an access code is entered or if the telephone line is restored.
If an alarm activates this output in the disarmed state, the out- put will deactivate if a user enters a valid access code while the Bell
NOTE: This output will activate for all silent and audible alarms except the Duress alarm and
[13] Kissoff Output
The output will activate for two seconds after the control panel receives the kissoff transmission from the central station.
[14] Ground Start Pulse
The PGM Output will activate for two seconds to obtain a dial tone on Ground Start telephone equipment before the panel attempts to dial. Insert two
[15] Remote Operation
This output can be activated and deactivated remotely using the DLS software.
[16] LINKS1000 Support (PGM1 Only)
The PGM output will be used as a data wire to communicate telephone number information for the LINKS1000 cellular unit.
[17] Away Armed Status
When the system is armed in the Away mode, the PGM output will activate at the beginning of the exit delay. The output deactivates when the panel is disarmed.
WWW.DIYALARMFORUM.COM