[349-350]

AC Line Trouble/Rest.

AC power to control panel is disconnected or inter-

MA/R

(3) A1

AT-00/AR-00

 

 

rupted/AC power restored (Both codes follow AC Fail-

 

 

 

 

 

ure Comm. Delay.)

 

 

 

 

 

 

 

 

 

[349-350]

Main Bell Trouble/Rest.

open circuit detected across bell terminals/bell circuit

MA/R

(3) 21

UT-99/UJ-99

 

 

closed

 

 

 

 

 

 

 

 

 

[349-350]

Fire Trouble/Rest.

a trouble occurs/restores on a fire zone

MA/R

(3) 73

FT-00/FJ-00

 

 

 

 

 

 

[349-350]

Auxiliary Power Trouble/

aux voltage supply trouble/restoral

MA/R

(3) AA

YP-00/YQ-00

 

Rest.

 

 

 

 

[349]

TLM Failure

telephone line monitoring trouble (sent via LINKS. Do

MA/R

(3) 51

LT-00

 

 

not program if LINKS not used)

 

 

 

 

 

 

 

 

 

[350]

TLM Restore

Telephone line trouble restore

MA/R

(3) 51

LR-00

 

 

 

 

 

 

[349-350]

Gen System Trouble/Rest.

“Service Required” trouble occurs (view troubles using

MA/R

(3) 33

ET-00/ER-00

 

 

[*][2])/trouble restored

 

 

 

 

 

 

 

 

 

[349-350]

Gen System Supervisory

control panel loses/restores communications with mod-

MA/R

(3) 33

ET-00/ER-00

 

Trouble/Rest.

ule(s) connected to the Keybus

 

 

 

 

 

 

 

 

 

[351]

Line 1 or 2 FTC Restoral

control panel has restored communications to central

MA/R

(3) 54

YK-00

 

 

station on line 1 or 2 (after FTC)

 

 

 

 

 

 

 

 

 

[351]

Event Buffer is 75% Full

event buffer is almost full since last upload

MA/R

(6) 23

JL-00

[351]

DLS Lead In

downloading session start

MA/R

(4) 11

RB-00

 

 

 

 

 

 

[351]

DLS Lead Out

downloading session complete

MA/R

(4) 12

RS-00

 

 

 

 

 

 

[351]

Zone Fault/Rest.

one or more zones have faults/restored

MA/R

(3) 72

UT-00/UJ-00

[351]

Delinquency

programmed amount of time (days or hours) for delin-

MA/R

(4) 54***

CD-00

 

 

quency has expired without zone activity or without sys-

 

 

 

 

 

tem being armed

 

 

 

 

 

 

 

 

 

[352]

Periodic Test

periodic system test transmission

T

(6) A2

RP-00

 

 

 

 

 

 

[352]

System Test

[*][6] bell/communications test

T

(6) A1

RX-00

[352]

LINKS Test

LINKS test transmission

T

(6) A3

TX-00

 

 

 

 

 

 

[353]

Wireless Device Low Bat-

wireless zones (WLS904, WLS905, WLS907); panic

MA/R

(3) 84

XT-00/XR-00

 

tery Trouble/Rest.

pendants (WLS908); handheld keypads (WLS910);

 

 

 

 

 

wireless keys (WLS909) have low battery/all low batter-

 

 

 

 

 

ies restored

 

 

 

 

 

 

 

 

 

*A/R = alarms/restorals; T/R = tampers/restorals; O/C = openings/closings; MA/R = miscellaneous alarms/restorals; T = test transmissions

**UU = user number (user01-42); ZZ = zone number (01-32)

***Program the “Fail to close” event code [(4)54] to report either closing or activity delinquency. Make sure your central station is aware of the application of this reporting code.

Table2: Contact ID Zone Alarm/Restoral Event Codes (as per ADEMCO):

Program any of these codes for zone alarms/restorals when using the standard (non-automatic) Contact ID reporting format.

Medical Alarms

(1)34

Entry / Exit

(1)AA

Medical

(1)35

Day / Night

(1)A1

Pendant Transmitter

(1)36

Outdoor

(1)A2

Fail to Report In

(1)37

Tamper

Fire Alarms

(1)38

Near Alarm

(1)1A

Fire Alarm

General Alarms

(1)11 Smoke

(1)4A

General Alarm

(1)12

Combustion

(1)43

Exp. module failure

(1)13

Water Flow

(1)44

Sensor tamper

(1)14 Heat

(1)45 Module Tamper

(1)15

Pull Station

(1)4A Cross Zone Police Code

(1)16

Duct

24 Hour Non-Burglary

(1)17 Flame

(1)5A

24 Hour non-Burg

(1)18 Near Alarm

(1)51 Gas detected

Panic Alarms

(1)52

Refrigeration

(1)2A

Panic

(1)53

Loss of Heat

(1)21 Duress

(1)54 Water Leakage

(1)22

Silent

(1)55

Foil Break

(1)23

Audible

(1)56

Day Trouble

Burglar Alarms

(1)57

Low bottled Gas level

(1)3A

Burglary

(1)58

High Temp

(1)31

Perimeter

(1)59

Low Temp

(1)32

Interior

(1)61

Loss of Air Flow

(1)33 24 Hour

Table 3: SIA Format Automatic Zone Alarm/Restoral Codes

 

 

SIA Auto Rep

Zone Definition

 

Codes*

 

 

 

 

 

Zone Alm/Rest.

 

 

 

Delay, Instant, Interior, Delay

 

BA-ZZ/BH-ZZ

Stay/Away, Interior Stay/Away,

 

 

24Hr Burg.

 

 

 

 

 

Standard 24Hr Fire, Delayed

 

FA-ZZ/FH-ZZ

24Hr Fire

 

 

 

 

 

24Hr Supervisory

 

US-ZZ/UR-ZZ

 

 

 

24Hr Supervisory Buzzer

 

UA-ZZ/UH-ZZ

 

 

 

24Hr Sprinkler

 

SA-ZZ/SH-ZZ

 

 

 

24Hr Gas

 

GA-ZZ/GH-ZZ

 

 

 

24Hr Heat

 

KA-ZZ/KH-ZZ

 

 

 

24Hr Medical

 

MA-ZZ/MH-ZZ

 

 

 

24Hr Emergency (non-medical)

 

QA-ZZ/QH-ZZ

 

 

 

24Hr Waterflow

 

WA-ZZ/WH-ZZ

 

 

 

24Hr Freeze

 

ZA-ZZ/ZH-ZZ

 

 

 

24Hr Holdup

 

HA-ZZ/HH-ZZ

 

 

 

24Hr Panic

 

PA-ZZ/PH-ZZ

 

 

 

Latching 24Hr

 

BA-ZZ/BH-ZZ

 

 

 

 

*

ZZ = zones 01-32

 

 

 