Outputs: |
|
|
|
Max. output current (relay contacts): | 1A | at | 24VDC |
| 0.5A |
| 50VDC |
Installation example:
Installation example with factory presets: see also “Factory preset sequences” page 36- 44
INPUTS:
All input signals must be applied longer than 200 msec. in order to be securely recognized. Modifying this default is possible in the menu “Trigger”.
A1 | Release signal: | Input for | |
A2 | General Stop: | Input (impulse); interrupts all currently running sequences | |
A3 | Alarm text: | Input (impulse) for playback alarm message (M00) | |
A4 | DIN alarm: | Input (impulse) for infinite DIN alarm (siren 1200 Hz - 500 Hz). | |
B1 | DIN alarm: | Key pressed for DIN alarm on, key released terminates the alarm | |
B2 | DIN alarm text: | Key pressed starts sequence, DIN alarm, 1 sec pause, alarm text (M00), | |
|
| 1 sec pause, DIN alarm, etc., key released terminates the sequence. | |
B3 | Input (impulse) starts a | ||
B4 | Input (static), key pressed starts | ||
|
| DMM 4650, key released terminates the sequence. | |
OUTPUTS: |
|
| |
All outputs are floating relay contacts. | |||
A1 | System on: |
| Switches on the electro acoustics sound reinforcement system. |
A2 | Alarm text running: |
| Signaling contact for alarm text active. |
A3 | Alarm signal running: | Signaling contact for alarm signal active. | |
A4 | Signaling contact for | ||
B1 |
| Signaling contact for | |
B2 | Mandatory relay E: |
| Switches the sound reinforcement system to mandatory reception (E). |
B3 | Mandatory relay D: |
| Switches the sound reinforcement system to mandatory reception (D). |
B4 | Program off: |
| Switches current music program off. |