Dynacord DMM 4650 owner manual Priority

Models: DMM 4650

1 52
Download 52 pages 40.35 Kb
Page 38
Image 38
Manual background

Sequence Nummer

Title

Priority

Stopp trigger

S 23

“DIN-Alrm”

95

B1 Low > 00,1s stc

Step

Command

Parameter

1:

Out

A1 set

2:

wt

In A1 High

3:

Out

B4 clr

4:

Out

B2 set

5:

Out

B3 set

6:

Out

A3 set

7:

Sum=

off

8:

DMM=

-5dB

9:

Start

A 20

10:

wt

Stop

11:End

Start DIN alarm (key B1 ON), Stop with key B1 OFF

Description: Turns the sound reinforcement system on (relay A1) and waits for acknowledgment (input A1 = system ready). When the system is ready, the output B4 (music program off) is opened and B2, B3 (mandatory reception E, D) gets closed. After closing the signaling contact (A3 = alarm signal running) the audio controls are set to alarm text priority. The output of the alarm signal (A20) is started. This sequence is terminated when the input B1 is Low (no current). Upon completion, the DMM 4650 returns to stand-by mode.

Sequence Nummer

Title

Priority

Stopp trigger

S 24

“Alrm-Txt”

91

B2 Low > 00,1s stc

Step

Command

Parameter

1:

Out

A1 set

2:

wt

In A1 High

3:

Out

B4 clr

4:

Out

B2 set

5:

Out

B3 set

6:

Out

A3 set

7:

Out

A2 set

8:

Sum=

off

9:

DMM=

-5dB

10:

Start

A 34

11:

wt

Audio

12:

Dly=

001,0s

13:

wt

Delay

14:

DMM=

-2dB

15:

Start

M 00

16:

wt

Audio

17:

Dly=

001,0s

18:

wt

Delay

19:

if

Stop

20:End

21:Jump 09

22:End

DIN alarm > alarm text > DIN alarm sequence, (start key B2 ON), Stop with key B2 OFF

Description: Turns the sound reinforcement system on (relay A1) and waits for acknowledgment (input A1 = system ready). When the system is ready, the output B4 (music program off) is being opened and B2, B3 (mandatory reception E, D) gets closed. After closing the signaling contacts (A3 = alarm signal, A2 = alarm text) the audio controls are set to alarm priority. The output in se- quence is: alarm signal 5 sec (A34) 1 sec. pause alarm text (M00) 1 sec. pause alarm signal 5 sec. (A34) 1 sec. pause, etc. until the input B2 = Low (no current) terminates the sequence. Upon termination the DMM 4650 returns to stand-by mode.

38

Page 38
Image 38
Dynacord DMM 4650 owner manual Priority