Dynacord DMM 4650 List of available step functions in sequences, Command, Function, parameter

Models: DMM 4650

1 52
Download 52 pages 40.35 Kb
Page 25
Image 25
List of available step functions in sequences

List of available step functions in sequences

Command

parameter

Function

Nop

 

 

-no operation

End

 

 

-ending the running sequence

Out

X.Y set

 

-Output Y (1 ..4) of the I/O module X (A..D) is set to 1 (contact closed)

 

X.Y clr

 

-Output Y (1 ..4) of the I/0 module X (A..D) is set to 0 (contact open)

 

X.Y inv

 

-Output Y (1 ..4) of the I/O module X (A..D) is inverted

Start

Axx

 

-ends a currently running audio signal immediately and starts the alarm preset xx

 

Gxx

 

-ends a currently running audio signal immediately and starts the gong preset xx

 

Mxx

 

-ends a currently running audio signal immediately and starts the message xx

 

Ann.

 

-ends a currently running audio signal immediately and starts the announcement

Break

 

 

-ends a currently running audio signal immediately

Finish

 

 

-requests the end of the running audio signal. Gong, alarm fade out, messages and

 

 

 

announcements are finished, recording is stopped.

DMM=

-xx dB

 

-controls of the DMM 4650 audio signal is set to -xx dB (*0 dB default)

Sum=

-xx dB

 

-control of the input - output XLR connection is set to -xx dB

Bypass

set

 

-analog bypass relay, direct connection XLR input - output closed

 

clr

 

-analog bypass relay, no relay connection XLR input - output

 

inv

 

-inverted analog bypass relay

Audio

prl

 

-switches the started DMM audio signals to pre-listen outputs (Pre-Listen only)

 

sum

 

-switches the started DMM audio signals to pre-listen and sum outputs (*default)

Record

Mxx

 

-ends a currently running audio signal immediately and starts the recording of the

 

 

 

message xx. At first this message is being erased and then recording starts at the last

 

 

 

adjusted recording level. Audio quality and name of this message stay unchanged.

 

 

 

The message priority is identical with the sequence priority. The execution time lasts

 

 

 

until End Delete Message (start of recording).

Dly=

ttt,t s

 

-sets a timer to ttt,t seconds and starts measuring this time (sand glass).

Count=

xxxx

 

-sets a counter (event counter) to a starting value xxxx. With every “if count”-command

 

 

 

the counter is decremented by 1 until 0 is reached.

Jump

xx

 

-resumes the sequence at step number xx.

if

Delay

 

-only executes the next step number if the delay time has elapsed (see command Dly).

 

 

 

Otherwise the next step number is being skipped.

 

Count

 

-the counter is decremented by 1. The next step number is executed only if the counter

 

 

 

has reached 0 (see command Count). If the counter value is greater than 0, the next

 

 

 

step number is being skipped.

 

Audio

 

-executes the next step number only if the audio signal started at last is finished

 

 

 

(see command start), otherwise the next step number is being skipped.

 

In X,Y

Z

-executes the next step number only if the desired level Z (H or L) is applied at input

 

 

 

Y (1 ..4) of the I/O module X (A..D). If this condition is not fulfilled, the next step number

 

 

 

is being skipped.

 

Stop

 

-executes the next step number only if the stop trigger condition of this sequence is

 

 

 

fulfilled. Otherwise the next step number is being skipped.

wt

Delay

 

-waits until the delay time is elapsed

 

Audio

 

-waits until the last started audio signal is finished

 

In X,Y

Z

-waits until the desired level Z (H or L) is applied at input Y (1 ..4) of the I/O

 

 

 

module X (A..D).

 

Stop

 

-waits until the stop trigger condition of this sequence is fulfilled.

* setting which is utilized, if a command is not used