Network Management Card – User Manual 34003991EN/EB Page 112/118
The NMC card implement reduce MGE Office Protection Systems MIB, with the objects bellow managed.
The entire MIB description is available on www.mgeops.com area “Downloads – Software Download.
Le chemin d’accès à la MIB MGE est 1.3.6.1.4.1.705.1.
MIB object SNMP Format Add.path
upsmgIdentFamilyName String {1,1,0}
upsmgIdentModelName String {1,2,0}
upsmgIdentFirmwareVersion String {1,4,0}
upsmgIdentSerialNumber String {1,7,0}
upsmgConfigLowBatteryTime seconds {4,7,0}
upsmgConfigLowBatteryLevel % {4,8,0}
upsmgConfigAutoRestart 1(yes) 2(no) {4,9,0}
upsmgConfigVARating VA {4,12,0}
upsmgBatteryRemainingTime seconds {5,1,0}
upsmgBatteryLevel % {5,2,0}
upsmgBatteryVoltage deciVolts {5,5,0}
upsmgBatteryCurrent deciAmps {5,6,0}
upsmgBatteryFaultBattery 1(yes) 2(no) {5,9,0}
upsmgBatteryReplacement 1(yes) 2(no) {5,11,0}
upsmgBatteryLowBattery 1(yes) 2(no) {5,14,0}
upsmgBatteryChargerFault 1(yes) 2(no) {5,15,0}
upsmgBatteryLowCondition 1(yes) 2(no) {5,16,0}
upsmgInputPhaseNum {6,1,0}
mginputVoltage_1 DeciVolts {6,2,1,2,1,0}
mginputVoltage_2 DeciVolts {6,2,1,2,2,0}
mginputVoltage_3 DeciVolts {6,2,1,2,3,0}
mginputFrequency_1 DeciHz {6,2,1,3,1,0}
mginputFrequency_2 DeciHz {6,2,1,3,2,0}
mginputFrequency_3 DeciHz {6,2,1,3,3,0}
mginputMinimumVoltage
{6,2,1,4,0}
mginputMaximumVoltage {6,2,1,5,0}
mginputCurrent_1 DeciAmps {6,2,1,6,1,0}
mginputCurrent_2 DeciAmps {6,2,1,6,2,0}
mginputCurrent_3 DeciAmps {6,2,1,6,3,0}
upsmgInputBadStatus {6,3,0}
upsmgInputLineFailCause {6,4,0}
upsmgOutputPhaseNum {7,1,0}
mgoutputPhaseIndex_1 {7,2,1,1,1,0}
mgoutputPhaseIndex_2 {7,2,1,1,2,0}
mgoutputPhaseIndex_3 {7,2,1,1,3,0}
mgoutputVoltage_1 deciVolts {7,2,1,2,1,0}
mgoutputVoltage_2 deciVolts {7,2,1,2,2,0}
mgoutputVoltage_3 deciVolts {7,2,1,2,3,0}