Network Management Card – User Manual 34003991EN/EB Page 112/118
8.2 SNMP objects 8.2.1 MGE MIB
The NMC card implement reduce MGE Office Protection Systems MIB, with the objects bellow managed.
The entire MIB description is available on www.mgeops.com area “Downloads – Software Download.
Le chemin d’accès à la MIB MGE est 1.3.6.1.4.1.705.1.
MIB object SNMP Format Add.path
upsmgIdentFamilyName String {1,1,0}
upsmgIdentModelName String {1,2,0}
upsmgIdentFirmwareVersion String {1,4,0}
upsmgIdentSerialNumber String {1,7,0}
upsmgConfigLowBatteryTime seconds {4,7,0}
upsmgConfigLowBatteryLevel % {4,8,0}
upsmgConfigAutoRestart 1(yes) 2(no) {4,9,0}
upsmgConfigVARating VA {4,12,0}
upsmgBatteryRemainingTime seconds {5,1,0}
upsmgBatteryLevel % {5,2,0}
upsmgBatteryVoltage deciVolts {5,5,0}
upsmgBatteryCurrent deciAmps {5,6,0}
upsmgBatteryFaultBattery 1(yes) 2(no) {5,9,0}
upsmgBatteryReplacement 1(yes) 2(no) {5,11,0}
upsmgBatteryLowBattery 1(yes) 2(no) {5,14,0}
upsmgBatteryChargerFault 1(yes) 2(no) {5,15,0}
upsmgBatteryLowCondition 1(yes) 2(no) {5,16,0}
upsmgInputPhaseNum {6,1,0}
mginputVoltage_1 DeciVolts {6,2,1,2,1,0}
mginputVoltage_2 DeciVolts {6,2,1,2,2,0}
mginputVoltage_3 DeciVolts {6,2,1,2,3,0}
mginputFrequency_1 DeciHz {6,2,1,3,1,0}
mginputFrequency_2 DeciHz {6,2,1,3,2,0}
mginputFrequency_3 DeciHz {6,2,1,3,3,0}
mginputMinimumVoltage
{6,2,1,4,0}
mginputMaximumVoltage {6,2,1,5,0}
mginputCurrent_1 DeciAmps {6,2,1,6,1,0}
mginputCurrent_2 DeciAmps {6,2,1,6,2,0}
mginputCurrent_3 DeciAmps {6,2,1,6,3,0}
upsmgInputBadStatus {6,3,0}
upsmgInputLineFailCause {6,4,0}
upsmgOutputPhaseNum {7,1,0}
mgoutputPhaseIndex_1 {7,2,1,1,1,0}
mgoutputPhaseIndex_2 {7,2,1,1,2,0}
mgoutputPhaseIndex_3 {7,2,1,1,3,0}
mgoutputVoltage_1 deciVolts {7,2,1,2,1,0}
mgoutputVoltage_2 deciVolts {7,2,1,2,2,0}
mgoutputVoltage_3 deciVolts {7,2,1,2,3,0}