4.4.3 Notified Applications
Click on "Notified Applications" in the menu.
Security: The administrator has to enter his/her login/password in order to view this information.
This menu enables:
◗The addition of the supervision stations receiving traps and configuration of the trap type.
◗To list all the Notified Applications and the main parameters.
◗To test the operation of notified applications
◗by simulating power loss
◗by sending a real shutdown sequence.
Up to 100 destinations can be managed by the card :
◗35 in TCP connected mode or
◗100 in UDP not connected mode or
◗mixed mode: 20 connected and 50 not connected.
Important note: It is not necessary to add the Network Shutdown Modules protecting your servers in this list. These modules subscribe and unsubscribe themselves automatically.
Select an entry in the list to modify the values in the edit zone at the bottom of the page. The table displays the following information:
◗The All button: Allows the following information to be displayed.
◗Nr is the index where the application is stored into the table.
◗Hostname or Address IP: By priority, the hostname of the computer is displayed when the IP address can be converted into a hostname by a DNS server or if the application has been entered as a hostname.
◗Application Name : Gived by the application at subscription time.
◗Output: number of the UPS output from which the client is powered.
◗Configuration: shows where the parameters of the Network Shutdown Module come from: Local (coming from the