7.4.3 Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT

7.4.3.1 Status table

Status description

Status to 0

Status to 1

Word (hex)

Bit

 

 

 

 

 

Load protected

no

yes

40

0

UPS coupled

no

yes

40

1

Unit general alarm

no

yes

40

2

UPS in backup

no

yes

40

4

Battery low warning

no

yes

40

5

Low battery

no

yes

40

6

Operation on static switch

no

yes

40

7

Communication fault

absent

present

40

9

UPS overload

no

yes

40

A

Emergency stop

absent

present

40

B

Battery to be checked

no

yes

40

D

Device ventilation fault

no

yes

40

E

Manual bypass switch (Q3BP)

open

closed

41

6

UPS in “eco” mode

no

yes

41

7

Battery present

absent

present

42

0

Mains 1 voltage out of tolerance

no

yes

44

8

Mains 1 fuse fault

no

yes

44

9

Mains 1 frequency out of tolerance

no

yes

44

B

Redundancy lost

no

yes

45

7

Maintenance position

no

yes

46

1

Mains 2 overload

no

yes

46

5

Mains 2 thermal overload

no

yes

46

6

Output on bypass

no

yes

46

7

Mains 2 frequency out of tolerance

no

yes

46

9

Mains 2 voltage out of tolerance

no

yes

46

A

Phase M2 out of tolerance

no

yes

46

B

Mains 2 internal fault

absent

present

47

2

Charger general fault

no

yes

49

0

Battery charge

no

yes

49

1 & 3

Converter fault

no

yes

4A

1

Inverter major fault

no

yes

4C

1

Inverter overload

no

yes

4C

2

Inverter thermal overload

no

yes

4C

3

Inverter limitation

no

yes

4C

4

UPS fuse fault

absent

present

4C

5

 

 

 

 

 