7.4.4.2 Modular fault table

Description du Status

Status to 0

Status to 1

Word

Bit

 

 

 

 

(hex)

 

 

 

 

 

 

 

Module 1

General alarm

Absent

Present

61

0

 

Fan failure

Absent

Present

61

1

 

Internal communication fault

Absent

Present

61

2

 

Inverter thermal overload

Absent

Present

61

3

 

Inverter fault

Absent

Present

61

4

 

Inverter fuse blown

Absent

Present

61

5

 

Load short circuit

Absent

Present

61

6

Module 2

General alarm

Absent

Present

62

0

 

Fan failure

Absent

Present

62

1

 

Internal communication fault

Absent

Present

62

2

 

Inverter thermal overload

Absent

Present

62

3

 

Inverter fault

Absent

Present

62

4

 

Inverter fuse blown

Absent

Present

62

5

 

Load short circuit

Absent

Present

62

6

Module 3

General alarm

Absent

Present

63

0

 

Fan failure

Absent

Present

63

1

 

Internal communication fault

Absent

Present

63

2

 

Inverter thermal overload

Absent

Present

63

3

 

Inverter fault

Absent

Present

63

4

 

Inverter fuse blown

Absent

Present

63

5

 

Load short circuit

Absent

Present

63

6

Module 4

General alarm

Absent

Present

64

0

 

Fan failure

Absent

Present

64

1

 

Internal communication fault

Absent

Present

64

2

 

Inverter thermal overload

Absent

Present

64

3

 

Inverter fault

Absent

Present

64

4

 

Inverter fuse blown

Absent

Present

64

5

 

Load short circuit

Absent

Present

64

6

 

 

 

 

 

 

 

 

 

 

 

 

Network Management Card – User Manual

34003991EN/EB

Page 98/118

Page 98
Image 98
Eaton Electrical 34003991EN/EB user manual Modular fault table