7.4.4.3 Measurements table

Description of the physical quantity

Word (hex)

Unit

 

 

 

 

 

I1 (I phase 1) mains 1

100

A

 

I2 (I phase 2) mains 1

101

A

I3 (I phase 3) mains 1

102

A

I1 (I phase 1) mains 2

106

A

I2 (I phase 2) mains 2

107

A

I3 (I phase 3) mains 2

108

A

I1 (I phase 1) output

109

A

I2 (I phase 2) output

10A

A

I3 (I phase 3) output

10B

A

I battery

10E

A

U12 mains 1

115

V

U23 mains 1

116

V

U31 mains 1

117

V

U mains 2 (phase 1)

11E

V

U mains 2 (phase 2)

11F

V

U mains 2 (phase 3)

120

V

U12 mains 2

121

V

U23 mains 2

122

V

U31 mains 2

123

V

U1N output

124

V

U2N output

125

V

U3N output

126

V

U12 output

127

V

U23 output

128

V

U31 output

129

V

U battery

12D

V

Output active power (phase 1)

130

W

Output active power (phase 2)

131

W

Output active power (phase 3)

132

W

Output apparent power (phase 1)

133

VA

Output apparent power (phase 2)

134

VA

Output apparent power (phase 3)

135

VA

Output total active power

136

W

Output total apparent power

137

VA

% output load level

139

%

 

Peak factor phase 1 x 100

13A

-

 

Peak factor phase 2 x 100

13B

-

 

Peak factor phase 3 x 100

13C

-

 

Power factor x 100

13D

-

 

Mains 1 frequency

13E

dHz

Mains 2 frequency

140

dHz

Output frequency

141

dHz

Battery backup time

149

Min

Battery charging level

14B

%

 

 

 

 

 

Network Management Card – User Manual

34003991EN/EB

Page 100/118

Page 100
Image 100
Eaton Electrical 34003991EN/EB user manual 100/118