The low alarm disappears when the value returns above the Low threshold + Hysteresis value
Input #1 and Input #2: Enter an identifier corresponding to the acquired contact (e.g.: rack door, air conditioning, generator unit, etc.). Max. length is 28 characters.
when closed and when open: are the names associated to the two contact positions. (e.g.: "open" and "closed" for a door, "On" and "Off" for a generator).
Each status change triggers a notification if enabled.
When the Notification box is enabled, the following functions are activated for each event selected:
◗display in the list of current alarms
◗Consideration in the UPS log
◗SNMP trap generation
◗notification by
The list of messages is given in the appendix
System shutdown can be triggered for each notification if this option is enabled. If notification is disabled, the Shutdown option cannot be used.
Export settings to file: Enables exportation ("Download" button) and saving of card configuration information.
Import settings from file: Enables selection of a configuration file ("Browse" button) and uploading ("Upload" button) of card configuration information.
Security: The user must be identified to access this page.
Network Management Card – User Manual | 34003991EN/EB | Page 63/118 |