7.4.5

Sensor data

 

 

 

 

 

 

 

 

7.4.5.1

Status table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Status description

 

Status to 0

 

Status to 1

Word (hex)

 

Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input 1 alarm

 

no

 

yes

45

 

5

 

 

 

Input 2 alarm

 

no

 

yes

45

 

6

 

 

 

Alarm : humidity too low

 

no

 

yes

45

 

4

 

 

 

Alarm : humidity too high

 

no

 

yes

45

 

3

 

 

 

Alarm : temperature too low

 

no

 

yes

45

 

2

 

 

 

Alarm : temperature too high

 

no

 

yes

45

 

1

 

 

 

Communication fault

 

no

 

yes

45

 

0

 

 

 

Input 1

 

open

 

close

48

 

0

 

 

 

 

 

 

 

 

 

Input 2

 

open

 

close

48

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network Management Card – User Manual

34003991EN/EB

Page 102/118

Page 102
Image 102
Eaton Electrical 34003991EN/EB user manual Sensor data, Status table