A.5 FRU State Management

The following table provides the SAM action, FRU status, hot swap state for each FRU

temperature sensor in the shelf.

Table A-1 FRU State Table for Nonrecoverable Threshold Events from Temperature Sensors

FRU Temperature Sensor SAM Action FRU Status
Step-1 Step-2 Operation
Hot Swap
State H/S LED
Active
SAM
Sensor # 6("MAX6656 INT
@1A")
Sensor # 7("MAX6656 EXT1
@1A")
Sensor # 8("MAX6656 EXT2
@1A")
Set all FAN-
module speed
MAX
H/S LED
ON. Still
working as
Active.
M6->M1
(Logical
SAM
(0x20) will
show M4
state)
Turn ON
Standby
SAM
Sensor # 6("MAX6656 INT
@1A")
Sensor # 7("MAX6656 EXT1
@1A")
Sensor # 8("MAX6656 EXT2
@1A")
Set all FAN-
module speed
MAX
H/S LED
ON.
M6->M1 Turn ON
PEM Sensor # 12 ("DS75 Temp") Set all FAN-
module speed
MAX
Issue
"deactivate"
command to
PEM
Still working. M6 > M1 Turn ON
ATCA -
F101
Sensor # 8 ("Inlet Temp") Set all FAN-
module speed
MAX
Issue
"deactivate"
command to
F101
Payload
powered
down by the
SAM.
M6 > M1 Turn ON
Sensor # 9 ("Outlet Temp") Set all FAN-
module speed
MAX
Issue
"deactivate"
command to
F101
Payload
powered
down by the
SAM.
M6 > M1 Turn ON
Sensor # 10 ("PMC Temp") Set all FAN-
module speed
MAX
Issue
"deactivate"
command to
F101
Payload
powered
down by the
SAM.
M6 > M1 Turn ON
Sensor # 20 ("Artesyn Temp") Set all FAN-
module speed
MAX
Issue
"deactivate"
command to
F101
Payload
powered
down by the
SAM.
M6 > M1 Turn ON