Table 3-3 - Switch SW2 (2-5), Output Rate Of Change

 

SW2-5

 

 

SW2-4

 

 

SW2-3

 

 

SW2-2

 

 

Nominal

 

 

 

 

 

 

 

 

 

 

Rate Of Change, ±15%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Close

Close

Close

Close

1.8 Min. Full Scale Travel

 

Close

Close

Close

Open

 

5.5 Min. Full Scale Travel

 

Close

Close

Open

 

Close

 

11.0 Min. Full Scale Travel

 

Close

Close

Open

Open

 

16.5 Min. Full Scale Travel

 

Close

Open

 

Close

 

Close

21.9 Min. Full Scale Travel

 

Close

Open

 

Open

 

Close

 

32.9 Min. Full Scale Travel

 

Close

Open

 

Open

 

Open

 

38.3 Min. Full Scale Travel

 

Open

 

Close

 

Close

Open

 

43.8 Min. Full Scale Travel

 

Open

 

Close

 

Open

 

Open

 

60.3 Min. Full Scale Travel

 

Open

 

Open

 

Close

 

Close

 

65.85 Min. Full Scale Travel

 

Open

 

Open

 

Close

 

Open

 

69.4 Min. Full Scale Travel

3.7 ANALOG FAILURE MODES (Fail Hold & Fail Zero)

Analog models have an "Analog Fault Detector" feature which, when selected by jumpers on the Termination Board, provides a selection of two failure modes, Fail Hold and fail Zero. In the "Fail Hold" mode, the Analog Fault will stop the stepper motor at the last pressure output value prior to the loss of the analog input signal. Note that the Guard terminals are not available for external usage in this mode. The Fault Detector trip point for this mode is factory set at 0.8 volts which corresponds to -5% of fullscale.

In the alternate "Fail Zero" mode, the Guard terminals are available for use with an external signal. In this mode, the analog input signal is “enabled” by a signal at the Guard terminal. If the input drops to zero while the Guard signal remains TRUE, the output will also go to zero.

The selection of either failure mode is accomplished via two jumpers, W1 and W2. These jumpers are located on the Termination Board as shown in Figure 3-2. These jumpers may be plugged in position A or B; however, both jumpers must always be in the same position.

The configurations are selected as follows:

FAIL-HOLD MODE

(Both Jumpers in A position)

In the "A" position, a failure of the AI Command Input (value fails below 0%) causes the pressure output to remain at the value of the last valid sampling period. This condition is maintained until a normal AI is received.

Board Setup

3-6

CI-9110

Page 30
Image 30
Emerson Process Management Series 9110 Analog Failure Modes Fail Hold & Fail Zero, Switch SW2 2-5, Output Rate Of Change