2.Reading on test gauge should be minimum range value (3 or 6 psi), ±5%.
3.Adjust input test circuit for 5.000 V.
4.Reading on test gauge should be maximum range value (15, 27 or 30 psi), ±5%.
5.If electronic calibration is correct but output pressure is in error, no further adjustments are possible. Refer to topic 5.2 for possible pneumatic faults.
6.Calibration is complete. Restore unit to normal operation.
Figure 5-3 - Raise/Lower Test Setup
5.8 DETAILED CALIBRATION FOR RAISE/LOWER MODEL
If calibration errors were found using the procedures of topic 5.6, the procedures described herein for Raise/Lower models are performed.
5.8.1 Feedback Zero & Span
The tracking voltage provided by the
1.Adjust input test circuit for minimum range indication on test gauge (3 or 6 psi).
2.DMM #1 should read 0.995 V, ±.004.
3.If reading of step 2 is out of tolerance, slightly loosen two screws on body of feedback pot (Figure
4.Adjust input test circuit for maximum range indication on test gauge (15, 27 or 30 psi).
Service |