3.1.1 Switch Functions

The Regulator assembly is configured by two, eight-switch packages which perform the functions listed in Table 3-1.

Table 3-1 - Regulator Assembly Switch SW1 & SW2 Functions & Settings

Switch

Switch

Page

*

**

Label
Function

Ref.

Your Setting

Your Notes

SW1-1

R/L % per pulse increment

3-4

 

 

SW1-2

R/L % per pulse increment

3-4

 

 

SW1-3

R/L % per pulse increment

3-4

 

 

SW1-4

R/L % per pulse increment

3-4

 

 

SW1-5

R/L % per pulse increment

3-4

 

 

SW1-6

Not Used

None

 

 

SW1-7

Not Used

None

 

 

SW1-8

Input Filter

3-4

 

 

SW2-1

Guard (Dynamic/Static)

3-5

 

 

SW2-2

Actuator Output Rate of Change

3-6

 

 

SW2-3

Actuator Output Rate of Change

3-6

 

 

SW2-4

Actuator Output Rate of Change

3-6

 

 

SW2-5

Actuator Output Rate of Change

3-6

 

 

SW2-6

Guard (Active/Inactive)

3-5

 

 

SW2-7

Not Used

None

 

 

SW2-8

Analog Input (V or I)

3-2

 

 

*Record your switch settings (ON or OFF) here for future reference.

**List your corresponding switch functions or values here.

3.2 ANALOG INPUT MODELS

Initially, it will be necessary to check the position of switches SW1-1 through SW1-5. These switches must be set to their OPEN positions to properly disable the functions associated with Raise/Lower models. The other uses of these switches are described under topic 3.3.

Analog models can be set to accept a 4-20 mA or 1-5 V dc signal at the Command Input. Switch SW2-8 selects these outputs as follows:

SW2-8

Analog Range

Close

4-20 mA dc

Open

1-5 V dc

3.3 RAISE/LOWER INPUT MODELS

Raise/Lower Actuator models can be set for continuous or incremental-type input signals via switches SW1-1 through SW1-5. The switch positions are shown in Table 3-2. The switch selections are described as follows:

Board Setup

3-2

CI-9110

Page 26
Image 26
Emerson Process Management 9110-00A, CI-9110 Analog Input Models, Raise/Lower Input Models, Switch Functions, Page, Label