Emerson Process Management CI-9110, 9110-00A Multiple DPC Cabinets Powered by Single Power Supply

Models: CI-9110 9110-00A Series 9110

1 74
Download 74 pages 60.74 Kb
Page 70
Image 70

1.Multi-Cabinet Instrument Grounding using Multiple Supplies. The instrument ground (24VRET terminal) of each DPC in a cabinet must connect to a terminal block within that cabinet that is electrically isolated from the cabinet frame. This terminal block must provide termination for all DPC instrument grounds within that cabinet and include termination for a #4 gauge (or greater), multistranded, insulated wire that will connect to the zero reference point of the facility. This #4 wire will be run through metal conduit (pipe) to the same termination point in the other cabinets. Only the #4 wire will be containe in this conduit. This conduit must also be connected by bonding strap to the cabinet and facility frame as described in the NEC.

2.Setting DPC Power Jumpers. If the DPC is a Model 3335 or 3310, jumpers W1A and W1B on the System Interconnect Board must be removed to isolate the chassis connection from the 24V RET connection (see Figure 8). If it is a Model 3330, jumpers W1A, W1B and W1C on the System Interconnect Board must be removed. Series 3308 Gas Flow Computers, if used with these systems, provide an isolated instrument ground without setting jumpers.

3.AC Power Source. The 24 Vdc power supply requires a 120 Vac power source. The ac power terminals of this supply are identified in Figure 8. The 120 Vac wiring for this supply must be contained in cable trays along with the power grid grounding wire. Figure 9 illustrates the cable tray layout and grounding points of a typical facility. The cabinet frame and the DPC chassis must be connected with bonding strap at points specified in the NEC.

4.Grounding of Peripheral Equipment. Some peripheral devices such as printers, CRTs, personal computers, etc., have their internal logic ground connected to the chassis. This configuration will cause loss of isolation between the DPC's instrument ground and chassis. These devices may still be used providing that opto-isolated circuits, galvanic isolation, or other types of circuitry between the device and the DPC are added to maintain the integrity of the DPC's "instrument ground to chassis" isolation.

Multiple DPC Cabinets Powered by Single Power Supply

All of the DPC cabinets in this installation operate from a single power supply which may be installed in one of the cabinets or in a separate cabinet. The following procedures apply:

1.Multi-Cabinet Instrument Grounding using Single Supply. The instrument ground (24VRET terminal) of each DPC in a cabinet must connect to a terminal block within that cabinet that is electrically isolated from the cabinet frame. This terminal block must provide termination for all instrument grounds within that cabinet and include termination for a multistranded, insulated, #4 gauge wire (or greater).

2.Routing of Instrument Ground and 24 V Power Wires. The #4 wire, along with +24V and 24VRET wires, are run through conduit trays to the power supply. The #4 wire connects to the 24VRET terminal of the supply and to the zero reference point of the facility. The +24V and 24RET wires connect to corresponding terminals on the power supply.

3.Cable Trays. Figure 9 illustrates the cable tray layout and grounding points of a typical facility. The cabinet frame and the DPC chassis must be connected with bonding strap at points specified in the NEC. The NEC also applies to the connection of the 120 Vac power supply terminals to the line.

12 / Supplement S1400

Page 70
Image 70
Emerson Process Management CI-9110, Series 9110, 9110-00A Multiple DPC Cabinets Powered by Single Power Supply