Emerson Process Management CI-9110, Series 9110, 9110-00A instruction manual Fail-Zero Mode

Models: CI-9110 9110-00A Series 9110

1 74
Download 74 pages 60.74 Kb
Page 31
Image 31
FAIL-ZERO MODE

FAIL-ZERO MODE

(Both Jumpers in B position)

In the "B" position (if the Guard signal remains TRUE), a failure of the AI Command Input signal (value fails below 0%) causes the pressure output to decay to 0% of scale and remain there until a normal AI is received. Should the Guard Input go FALSE prior to the AI command failure, the last pressure output value will be held.

Figure 3-2 - Jumper Location on Analog Termination Board

CI-9110

3-7

Board Setup

Page 31
Image 31
Emerson Process Management CI-9110, Series 9110, 9110-00A Fail-Zero Mode, 2 - Jumper Location on Analog Termination Board