Fluke 1625 user manual Selective Measurement of the Earthing Resistance REA, Earth/Ground Tester

Models: 1625

1 90
Download 90 pages 25.79 Kb
Page 25
Image 25
Selective Measurement of the Earthing Resistance (REA)

Earth/Ground Tester

Specifications

Selective Measurement of the Earthing Resistance (REA)

Measuring method:

Current and voltage measurement with probe as per

 

 

 

EN61557-5 and current measurement in the individual

 

 

 

branch with additional current transformer (patent ap-

 

 

 

plied for).

 

 

 

Open circuit volt-

20 / 48 V AC

 

 

age:

 

 

 

 

 

Short circuit current:

250 mA AC

 

 

Measuring fre-

 

94, 105, 111, 128 Hz selected manually or automati-

quency:

 

cally (AFC), 55 Hz (R*)

 

 

Noise rejection:

120 dB (16 2/3 , 50 , 60 , 400 Hz)

 

Max. overload:

 

max. Urms = 250 V (measurement will not be started)

 

 

 

 

 

 

 

Measuring

 

Display Range

Resolution

Intrinsic

Operating

Range

 

Error *

Error *

 

 

 

 

 

 

 

 

 

 

 

 

0.001...2.999

0.001

 

 

 

 

 

 

 

 

 

 

3.00...29.99

0.01

 

 

 

 

 

 

 

 

0.020 ...

 

30.0...299.9

0.1

± (7 % of

± (10% of m.v.

 

 

 

 

 

m.v. +2

+5 digit)

30 k

 

0.300...2.999 k

1

 

digit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.00...29.99 k

10

 

 

 

 

 

 

 

 

 

* With recommended current clamps / transformers.

Additonal error because of probe- and auxiliary earth typ.electrode resis- tance:

Measuring error of RH and RS:

Measuring time:

RH (RS + 2000Ω) ⋅1.25 ⋅10−6 % + 5digits

RETOTAL

typ.of 10% of RETOTAL + RS + RH

typ. 8 sec. with a fixed frequency 30 sec.max. with AFC and complete cycle of all measuring frequencies

17

Page 25
Image 25
Fluke 1625 Selective Measurement of the Earthing Resistance REA, RH RS + 2000Ω ⋅1.25 ⋅10−6 % + 5digits, Specifications