Accordingly, these equivalent resistances are displayed as:

REi = U meas

li

Therefore the earthing resistance RE of the pylon is determined as a parallel circuit of the individual equivalent resistances:

RE

=

 

 

 

1

 

 

 

1

+

1

+

1

+

1

 

 

 

 

RE1

 

R E 2

 

RE3

 

RE 4

 

 

1625 EARTH / GROUND TESTER

 

 

 

 

 

 

 

START

 

H/C2

 

 

 

 

 

 

TEST

 

 

 

 

 

 

 

DISPLAY

 

S/P2

 

 

 

 

 

 

MENU

 

 

 

 

 

 

 

 

AC

 

 

 

 

 

 

 

Earth/Ground Resistance 300 k

Resistance

 

 

 

 

 

 

 

300 k DC Low Resistance 3k

 

 

 

 

 

 

RA

R

R

 

 

 

 

 

 

4 POLE

2 POLE

 

 

 

 

 

 

 

2 POLE

 

 

 

 

 

 

3 POLE

 

 

 

 

 

 

4 POLE

 

4 POLE

 

 

 

 

 

 

CHANGE

 

ES/P1

 

 

 

 

 

 

ITEM 3 POLE

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

SELECT

 

E/C1

 

 

 

 

4 Pole

 

Auxiliary

Probe

earth

electrode

>20 m

 

>20 m

edw016.eps

Figure 13. Measuring the Earthing Resistance without Disengaging the

Overhead Earth Wire

1.Turn central rotary switch to position “ARE 3pole" or ARE 4pole". The instrument is to be wired according to picture and notices given on the display.

A flashing of the sockets symbols EFGHor B, points to an incorrect or incomplete connection of the measuring lead.

2.Apply current transformer to the pylon stub. Make sure that the trans- formation ratio set on the instrument corresponds to the current trans- former used. Change settings if necessary (see “Changing of All Data Settings with Personalised CODE”)