Fluke 1625 user manual Operation, Use only current transformers referred to in this manual

Models: 1625

1 90
Download 90 pages 25.79 Kb
Page 76
Image 76
Operation

1625

Users Manual

Operation

Connect the adapter according to the diagram and the designations E, S and H (C1, P1 and P2 for US-version) to the tester and to a current clamp.

 

1625 EARTH / GROUND TESTER

START

 

 

H/C2

TEST

 

 

 

DISPLAY

 

 

S/P2

MENU

 

 

 

 

AC

 

 

Earth/Ground Resistance 300 k

Resistance

DC Low Resistance 3k

 

300 k

 

RA

R

R

 

4 POLE

2 POLE

 

 

 

2 POLE

 

3 POLE

 

 

4 POLE

 

4 POLE

CHANGE

3 POLE

 

ES/P1

ITEM

 

 

 

OFF

 

 

SELECT

 

 

E/C1

H

S

E

Black

EI-162AC

Red

EI-162X

edw063.eps

Use the test cable contained in the set to connect the second current clamp to the socket. Ensure that connections are in the correct polarity. Turn the rotary switch of the tester to position RE D3 pole.

Note

Use only current transformers referred to in this manual.

Clamp both transformers around the ground conductor to be tested.

Note

Try to have a distance > 10 cm between the clamps for optimal re- sults.

68

Page 76
Image 76
Fluke 1625 user manual Operation, Use only current transformers referred to in this manual