| Stakeless Earth/Ground Resistance Testing |
| Principle of Operation |
|
|
Dimensions | Total length of adaptercable 1,8 m, Length |
| of shielded cable to |
Operating error*: | ± (10% of m.v. + 5 digit). |
Display range*: | 0,010 Ω ... 130 Ω. |
Measuring frequency: | 128 Hz. |
Measuring voltage: | Um=48 VAC (primary). |
Measuring range*: | 0,020 Ω ... 100 Ω. |
Resolution: | .001... .1 ohm. |
*when using: | CT |
| CT |
| Recommended distance between CT's: |
| 10 cm. |
Principle of Operation
Purpose
Testing the resistances of individual ground connections in systems with paral- lel ground connections
65