Fluke 1625 Measurement of Soil Resistivity, Earth/Ground Tester, Procedure of Measurements

Models: 1625

1 90
Download 90 pages 25.79 Kb
Page 53
Image 53
Measurement of Soil Resistivity

Earth/Ground Tester

Procedure of Measurements

3.Call display RK with "DISPLAY MENU" button.

4.Implement compensation with "START TEST" button.

The compensation resistance is displayed only for as long as the "START TEST" button is kept pressed. After releasing the "START TEST" button the measured value is stored and the measuring instrument returns to the standard settings at the beginning of the measurement so that a succeeding measurement of the earthing resistance can be implemented by pressing "START TEST" again. Thereafter, RK is subtracted from the actual measured value.

If the compensation value has to be reset to the basic setting (0.000 Ω), the compensation sequence has to be implemented with an open (disconnected) measuring lead or turn the switch to the next position and back.

Measurement of Soil Resistivity

The soil resistivity is the geological and physical quantity for calculation and design of earthing systems. The measuring procedure applied below uses the method developed by Wenner (F.Wenner, A method of measuring earth resis- tivity; Bull. National Bureau of Standards, Bulletin 12 (4), Paper 258, S 478- 496; 1915/16).

Manual background 1625 EARTH / GROUND TESTER

START TEST

DISPLAY MENU

H/C2

S/P2

 

AC

 

Earth/Ground Resistance 300 k

Resistance

DC Low Resistance 3k

300 k

RA

R

R

2 POLE

4 POLE

 

3 POLE

2 POLE

 

4 POLE

4 POLE

CHANGE

3 POLE

ES/P1

ITEM

 

OFF

SELECT

E/C1

edw020.eps

Figure 16. Measurement of Soil Resistivity

45

Page 53
Image 53
Fluke 1625 user manual Measurement of Soil Resistivity, Earth/Ground Tester, Procedure of Measurements