Earth/Ground Tester
Procedure of Measurements
2.Connect instrument according to picture.
3.In this mode, all settings and LIMIT values available can be called with "DISPLAY MENU" and the measuring frequency can be set.
4.Press "START TEST" button.
5.Read out measured value.
Resistance Measurement (RF)
In this measuring mode all resistances from 0.001 Ω to 3 kΩ can be measured with DC voltage and automatic polarity reversal as per
To achieve highest accuracy 4 pole measurements are possible. To balance the extension lead, a compensation has to be done.
| 1625 EARTH / GROUND TESTER | ||
START |
|
| H/C2 |
TEST |
|
|
|
DISPLAY |
|
| S/P2 |
MENU |
|
| |
|
| AC |
|
| Earth/Ground Resistance 300 k | Resistance | DC Low Resistance 3k |
| 300 k | ||
| RA | R | R |
| 4 POLE | 2 POLE |
|
|
| 2 POLE | |
| 3 POLE |
| |
| 4 POLE |
| 4 POLE |
CHANGE | 3 POLE |
| ES/P1 |
ITEM |
|
| |
| OFF |
|
|
SELECT |
|
| E/C1 |
|
|
| edw024.eps |
Figure 18. Resistance Measurement (RF)
1.Connect instrument according to picture.
2.Turn central rotary switch to position "RF".
3.In this mode, all settings and LIMIT values available can be called with "DISPLAY MENU".
WWarning
Before starting a measurement bring plant or test object to off or
49