Fluke 1625 Earth/Ground Tester, Procedure of Measurements, restivity, Soil, Distances of Probe

Models: 1625

1 90
Download 90 pages 25.79 Kb
Page 55
Image 55
restivity

Earth/Ground Tester

Procedure of Measurements

 

1

 

 

2

3

E

 

 

restivity

 

 

Soil

A

 

 

Distances of Probe

 

edw021.eps

Curve 1: As ρE decreases only deeper down, a deep earth electrode is advis- able

Curve 2: As ρE decreases only down to point A, an increase in the depth deeper than A does not improve the values.

Curve 3: With increasing depth ρE is not decreasing: a strip conductor elec- trode is advisable.

As measuring results are often distorted and corrupted by underground pieces of metal, underground aquifers etc, a second measurement, in which the spike axis is turned by an angle of 90 ° , is always advisable (see picture).

47

Page 55
Image 55
Fluke 1625 user manual Earth/Ground Tester, Procedure of Measurements, restivity, Soil, Distances of Probe, edw021.eps