VERT-I-PAK INSTALLATION RECOMMENDATIONS
FORPROPERUNITPERFORMANCEANDMAXIMUMOPERATINGLIFEPLEASEREFERTOTHEMINIMUMINSTALLATIONCLEARANCES BELOW.
FIGURE 1
6" |
| B |
|
|
60" 60" | A |
|
| |
|
|
| ||
SMALL RECESS OK | LARGER RECESS OK. IF A> 5XB | 60" | 60" | |
|
| |||
60" |
|
| 60" |
|
|
|
|
| |
60" | 60" |
| 60" |
|
|
|
|
| |
60" | 60" |
|
|
|
6" | 6" |
|
| 12" |
|
|
|
|
FIGURE 2
ANY TIME OBSTRUCTIONS ARE PRESENT USE THE FOLLOWING GUIDELINES FOR PROPER SPACING FROM THE
•FOR MINOR OBSTRUCTION SUCH AS LAMP POLES OR SMALL SHRUBBERY A CLEARANCE OF 24” FROM THE OUTDOOR LOUVER SHOULD BE MAINTANED.
•FOR MAJOR OBSTRUCTIONS SUCH AS A SOLID FENCE, WALL OR OTHER HEAT REJECTING DEVICE LIKE A CONDENSING UNIT, A MINIMUM DISTANCE OF 72” SHOULD BE KEPT.
BUILDING
60" | 24" |
|
VPAK | 12" VPAK | VPAK |
|
| 24" |
| POLE | SHRUB |
|
| |
OUTDOOR |
| 72" |
CONDENSING |
|
|
UNIT | FENCE |
| |
| MAJOR OBSTRUCTION |
THE ABOVE SUGGESTIONS ARE FOR REFERENCE ONLY AND DO NOT REPRESENT ALL POSSIBLE INSTALLATIONS. PLEASE CONTACT FRIEDRICH AIR CONDITIONING
(SEE CONTACT INFORMATION ON BACK COVER) FOR INFORMATION REGARDING AFFECTS OF OTHER INSTALLATION ARRANGEMENTS.
BY FOLLOWING THESE SIMPLE RECOMMENDATIONS YOU CAN BE CONFIDENT THAT YOUR FRIEDRICH