REMOTE THERMOSTAT AND LOW VOLTAGE CONTROL CONNECTIONS
REMOTE THERMOSTAT
ALL FRIEDRICH
TO CONNECT THE
1.PULL THE DISCONNECT SWITCH.
2.UNSCREW AND REMOVE THE CONTROL BOX PANEL.
3.AFTER SELECTING WHICH SIDE YOU WANT TO RUN YOUR THERMOSTAT WIRE THROUGH, RUN THE WIRES THROUGH THE SIDE HOLE IN THE BOX TO REACH THE CONNECTION TERMINAL FOR THE WIRING.
4.MAKE THE WIRE CONNECTIONS, APPROPRIATELY MATCHING THE WIRES AS SHOWN IN THE WIRING DIAGRAM.
5.ONCE EACH WIRE IS MATCHED AND CONNECTED, THE UNIT IS NOW READY FOR OPERATION.
6.REATTACH THE CONTROL BOX COVER.
DESK CONTROL TERMINALS
THE FRIEDRICH
FOR DESK CONTROL OPERATION, CONNECT ONE SIDE OF THE SWITCH TO THE D1 TERMINAL AND THE OTHER TO THE D2 TERMINAL (SEE FIGURE 15). WHENEVER THE SWITCH CLOSES, THE UNIT OPERATION WILL STOP.
NOTE: THE DESK CONTROL SYSTEM AND SWITCHES MUST BE FIELD SUPPLIED.
MAXIMUM WIRE LENGTH FOR DESK CONTROL SWITCH
WIRE SIZE | MAXIMUM LENGTH |
|
|
#24 | 400 FT. |
#22 | 600 FT. |
#20 | 900 FT. |
#18 | 1500 FT. |
#16 | 2000 FT. |
AUXILIARY FAN CONTROL
NOTE: IT IS THE INSTALLER’S RESPONSIBILITY TO ENSURE THAT ALL CONTROL WIRING CONNECTIONS ARE MADE IN ACCORDANCE WITH THE INSTALLATION INSTRUCTIONS. IMPROPER CONNECTION OF THE THERMOSTAT CONTROL WIRING AND/OR TAMPERING WITH THE UNIT’S INTERNAL WIRING CAN VOID THE EQUIPMENT WARRANTY AND MAY RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. OTHER MANUFACTURER’S UNITS AND EVEN OLDER FRIEDRICH MODELS MAY HAVE DIFFERENT CONTROL WIRING CONNECTIONS. QUESTIONS CONCERNING PROPER CONNECTIONS TO THE UNIT SHOULD BE DIRECTED TO THE FACTORY.
CONTROL BOARD
FIGURE 14
| Interface Definition | |
Terminal Code |
| Wire Connection Function |
C |
| COMMON GROUND TERMINAL |
GH |
| CALL FOR HIGH FAN |
GL |
| CALL FOR LOW FAN |
B |
| CALL FOR HEAT PUMP REVERSING VALVE |
Y |
| CALL FOR COMPRESSOR |
W |
| CALL FOR HEATING |
R |
| 24V POWER FROM ELECTRONIC CONTROL TO WALL |
| THERMOSTAT | |
|
| |
|
|
|
THE SMART CENTER ALSO HAS THE ABILITY TO CONTROL A 24VAC RELAY TO ACTIVATE AN AUXILIARY, OR TRANSFER, FAN. THE OUTPUTS ARE LISTED AS F1 AND F2 ON THE CONTROL BOARD.
TO CONNECT THE RELAY, SIMPLY WIRE ONE SIDE OF THE RELAY TO F1 AND THE OTHER SIDE TO F2. ANYTIME THAT THE FAN RUNS, THE TERMINALS WILL SEND A 24VAC SIGNAL TO THE RELAY. THE RELAY MUST BE 24VAC, 100MA OR LESS.
NOTE: THE RELAY AND AUXILIARY FANS MUST BE FIELD SUPPLIED.
12