Frymaster 45, 35 manual The Electronic Circuits, The Gas Valve, Improper Burner Function

Models: 45 35

1 76
Download 76 pages 43.51 Kb
Page 21
Image 21

The Electronic Circuits

If the fryer is receiving gas and electrical power, the next most likely cause of ignition failure is a problem in the 24 VAC circuit of the pilot system. If the fryer is equipped with a drain valve for filtration purposes, check the drain valve to verify that it is fully closed. A microswitch attached to the valve must be closed for power to reach the gas valve. Often, although the valve handle appears to be in the closed position, the microswitch is still open. If the valve is fully closed, or the fryer is not equipped with a filtration system, refer to Troubleshooting the 24 VAC Circuit in Section 1.7.1 of this manual.

The Gas Valve

If the problem is not in the 24 VAC circuit of the pilot system, it is most likely in the gas valve. However, before replacing the gas valve, refer to Troubleshooting the Gas Valve in Section 1.7.2 of this manual.

Improper Burner Function

In these types of instances, the burner ignites but exhibits abnormal characteristics, such as popping, incomplete lighting of the burner, fluctuating flame intensity, and flames “rolling” out of the fryer.

Popping indicates delayed ignition. In most cases, the main gas valve is opening, but the burner is not immediately lighting. When ignition does take place, excess gas bursts into flame suddenly, rather than smoothly igniting.

The primary causes of popping are:

1.Incorrect or fluctuating gas pressure

2.Misdirected or weak pilot flame

3.Clogged burner orifices

4.Inadequate make-up air

5.Missing or misaligned burner deflector targets

6.Clogged vent tube (causing incorrect gas pressure).

Incorrect or Fluctuating Gas Pressure

If popping occurs only during peak hours, the problem may be incorrect or fluctuating gas pressure. Verify that the incoming gas pressure (to the gas valve) is in accordance with the appropriate CE or non- CE standard found in the table on Page 1-4 and the pressure remains constant throughout all hours of usage. Refer to Checking the Burner Manifold Pressure in Section 1.3.2 for instructions on checking the pressure of gas supplied to the burner.

Misdirected or Weak Pilot Flame

If popping is consistent during all hours of operation, check position of the pilot above the burner orifice and verify that the pilot pressure is correct. A 1- to 1 ½-inch (25 to 38 mm) flame indicates correct pilot pressure. Refer to Section 1.3.3 for information on pilot flame adjustment.

Clogged Burner Orifices

1-16

Page 21
Image 21
Frymaster 45, 35 The Electronic Circuits, The Gas Valve, Improper Burner Function, Incorrect or Fluctuating Gas Pressure