Gas-Fired Products PTS Series, PTU Series manual Vertical

Models: PTS Series PTU Series

1 54
Download 54 pages 34.59 Kb
Page 40
Image 40
Vertical

In multiple heater applications, the combustion air intake may be ducted individually or common ducted in the same configuration as shown for venting in Section 16.0. For combustion air intake duct sizing, please refer to the Vent Sizing Table and use the diameter indicated, based on the number of heaters per duct.

Vertical

 

Through the roof

Combustion Air Cap

 

(Leslie VersaCap

 

Type B)

3 ft. (91cm)

4” Diameter

Minimum

Single-Wall Pipe

Flashing

 

 

4” Spring

 

Tension Clamp (2 each)

Horizontal

(Part No. 30676040)

Through Sidewall

 

 

4” Starting Collar

Burner Box (side view)

 

1/4” (6mm)

 

6” (15cm)

per ft. slope downwards

4” Flexible Air Inlet Hose

towards vent terminal

Minimum

 

2 Ft. Long

 

 

(Part No. 30675020)

SIDE VIEW

(straight configuration)

Combustion Air Intake

Flue vent termination must be 1 ft. (30 cm) higher than combustion air inlet cap.

Form #43343330

 

May 08

–39–

Page 40
Image 40
Gas-Fired Products PTS Series, PTU Series manual Vertical