Nonincendive Field Wiring (Control Drawing #DR00)

Hazardous (Classified) Location Class I,

Division 2 Groups A, B, C, and D

USB Port PL6

USB Port PL6

USB Port PL10

Ethernet Port

Panel C

Keyboard Port

Mouse Port

Non-hazardous Area

Associated Nonincendive Field Wiring Apparatus

1

Notes:

1. Nonincendive Circuit Parameters:

Panel C Industrial Computer

Vmax = 5VDC

Voc = 5 VDC

Imax = 500mA

Isc = 500mA

Ci = 34.2µF

Ca = 1000µF

Li = 0mH

La = 5mH

2.Selected Associated Nonincendive Field Wiring Apparatus must satisfy the following requirements:

Associated Nonincendive

 

Panel C

Field Wiring Apparatus

 

Industrial Computer

Voc

Vmax

Isc

Imax

C a

Ci + C cable

La

Ci + C cable

Vmax

Voc

Imax

Isc

Ci + Ccable

Ca

Li + Lcable

La

3.If the electrical parameters of the cable are unknown, the following values may be used:

Capacitance – 60 pF/ft

Inductive – 0.20 µH/ft

4.Nonincendive Field Wiring must be installed in accordance with Article 501.4(B)(3) of the National Electrical Code ANSI/NFPA 70.

A-4

Panel C Industrial Computer Hardware User's Manual–May 2003

GFK-2251

Page 60