Heat Controller VMH24SC-1, VMH12SC-1, VMH09SC-1, VMH18SC-1 service manual VMH Series, Defrost mode:

Models: VMH18SC-1 VMH09SC-1 VMH24SC-1 VMH12SC-1

1 45
Download 45 pages 50.02 Kb
Page 29
Image 29
8.4.3.4 Defrost mode:

Heat Controller, Inc.

VMH Series

Service Manual

 

 

 

Auto fan action in heating mode.

T1-Ts-ΔT

 

°F

°C

(2.5)

(2.0)

(1.5)

(1.0)

 

 

8.4.3.4 Defrost modeManual background

Conditions of defrost:

When the unit is running, if any one of the following conditions is satisfied, the unit starts defrost:

1 .Defrost is available after 40 minutes of run time if T3 (Condenser coil temperature) is37°F/3°C and there is a 11°F/6°C temperature difference for 3 minutes.

2.Defrost is available after 80 minutes of run time if T3 (Condenser coil temperature) is37°F/3°C and there is a 7°F/4°C temperature difference for 3 minutes.

3.Defrost is available after 120 minutes of run time if T3 Condenser coil temperature) is37°F/3°C and there is a 4°F/2°C temperature difference for 3 minutes.

4.If any of the above conditions are satisfied and the T2 (Evaporator coil temperature) has decreased 9°F/5°F below the normal maximum indoor pipe temperature, unit starts defrost.

Note: T2 is the maximum value of the evaporator temperature during the anti-cold wind function. It’s recorded by the system automatically.

Terminating defrost:

If any one of following items is satisfied, defrost will stop and unit will return to normal heating mode. 1 .Defrost time has reached 10 minutes

2 .T3 (Condenser coil temperature) >46°F/8°C for 80 seconds.