8.4.2 Cooling Mode

Service Manual

VMH Series

Heat Controller, Inc.

 

 

 

8.4.2 Cooling Mode

8.4.2.1 Compressor running rules:

The operating frequency of compressor after starting submits to following rule.

T4

°F °C

113(45)

109(43)

104(40)

100(38)

86(30)

82(28)

72(22)

68 (20)

If users switch on A/C by remote controller, the compressor will run at the Fmax frequency for 7 minutes according to outdoor ambient temp. During the 7 minutes, frequency limitation is active.

7 minutes later, the compressor running frequency will be controlled as below:

T1-Ts

 

°F

°C

38

(3.5)

37

(3.0)

37

(2.5)

36

(2.0)

40

(1.5)

34

(1.0)

33

(0.5)

29

(-0.5)

30

(-1.0)

While

Temp. zone

A

B

C

D

E

F

G

Frequency

F8

F8

F7

F6

F5

F3

F1

22

Page 22
Image 22