Heat Controller, Inc.

VMH Series

Service Manual

 

 

 

6.3 Pressure Test & Evacuation

Air and moisture in the refrigerant system have undesirable effects as below:

Pressure in the system rises.

Operating current rises.

Cooling or heating efficiency drops.

Moisture in the refrigerant circuit may freeze and block capillary tubing.

Refrigerant lines and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined is followed.

1. System Evacuation and Charging

(Indoor unit)

(Liquid side)

(Outdoor unit)

 

 

 

 

Two-way valve

 

 

Close

 

(Gas side)

 

Manifold valve

Three-way valve

Close

500 Microns

 

Lo

Hi

Low Side

HI Side

Charge hose

Charge hose

Vacuum

 

pump

 

Vacuum

 

pump

 

1)Completely tighten the flare nuts of the indoor and outdoor units, connect manifold gauge low side hose to low side service valve.

2)Connect the manifold gauge charge hose to the vacuum pump.

3)Fully open the low side of manifold gauge.

4)Start vacuum pump.

5)Evacuate using either deep vacuum or triple evacuation method.

6)After evacuation is complete, fully close the low side of manifold gauge and shut off vacuum pump.

7)The factory charge contained in the outdoor unit is good for up to 16.5 ft. of line length. For line set lengths over 16.5 ft., adjust charge according to chart in section 6.2.

8)Disconnect charge hose from low side service valve.

9)Fully open both high and low side service valves and securely tighten caps.

17

Page 17
Image 17
Heat Controller VMH24SC-1, VMH12SC-1, VMH09SC-1, VMH18SC-1 Pressure Test & Evacuation, System Evacuation and Charging