8.4.5 Dehumidify mode
8.4.5.1Indoor fan speed is fixed in breeze and can’t be changed. The louver angle is the same as in cooling mode.
8.4.5.2Compressor running rules
°F °C
36.5(2.5)
35.6(2.0)
34.7(1.5)
33.8(1.0)
32.9(0.5)
32 (0.0)
8.4.5.3Room low temperature protection
If room temperature is lower than 50°F/10°C, compressor will stop and not resume operation until room temperature is over 54°F/12°C.
8.4.5.4Evaporator
8.4.5.5The outdoor fan operates same as in cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
Pressing the touch button once, the machine will transfer into forced auto mode, pressing the button once again, the machine will turn into forced cooling mode, the third press will stop the unit, and the forth press is the start of the cycle of forced auto mode. Refer to the following chart: