8.4.2.5 Evaporator low temperature T2 protection.

When T2<32°F/0°C, the compressor will stop and restart when T2>41°F/5°C.

When 32°F/0°C≤T2<39°F/4°C, the compressor frequency is limited and decreases to the lower level every minute until stop the compressor stops.

When 39°F/4°C ≤T2≤45°F/7°C, the compressor will keep the current frequency.

When T2>45°F/7°C, the compressor frequency will not be limited.

8.4.3 Heating Mode

8.4.3.1 Compressor running rules:

The operation frequency of compressor after starting submits to following rule.

T4

 

°F

°C

93

(34)

91

(33)

82

(28)

81

(27)

77

(25)

75

(24)

72

(22)

70

(21)

66

(19)

64

(18)

63

(17)

61

(16)

59

(15)

57

(14)

54

(12)

52

(11)

43

(6)

41

(5)

 

 

25

Page 25
Image 25
Heat Controller VMH24SC-1, VMH12SC-1 Evaporator low temperature T2 protection, Heating Mode Compressor running rules