Service Manual | VMH Series | Heat Controller, Inc. |
|
|
|
P1:
9.2.7 Over voltage or too low voltage protection diagnosis and solution
Is the power supply good?
Yes
No
Make sure the power supply is normal.
Replace the outdoor
P2:
9.2.8 High temperature protection of compressor top diagnosis and solution
|
|
|
|
| No |
|
|
|
| |
| Does the compressor operate? |
|
|
| Is the connection good? |
| ||||
|
|
|
|
|
|
| ||||
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
| Yes |
|
|
|
| Yes | ||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
| Is refrigerant circulation |
|
|
|
|
|
|
|
|
|
| charge correct? |
|
|
|
| Is overload protector normal? |
| |||
|
|
|
|
|
|
|
|
| ||
| No, |
|
|
|
|
|
| |||
| Charge refrigerant |
|
|
|
| Yes | ||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
| Is the abnormality the same |
|
|
|
|
|
|
|
| |
| after gas charging? |
|
|
|
|
| Replace the outdoor PCB. | |||
|
|
|
|
|
|
|
|
|
|
|
There is a restriction (Such as capillary or welded points of the pipes.)
No
No
Reconnect and retest
Replace it
40