P1:

9.2.7 Over voltage or too low voltage protection diagnosis and solution

Is the power supply good?

Yes

No

Make sure the power supply is normal.

Replace the outdoor e-box.

P2:

9.2.8 High temperature protection of compressor top diagnosis and solution

 

 

 

 

 

No

 

 

 

 

 

Does the compressor operate?

 

 

 

Is the connection good?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is refrigerant circulation

 

 

 

 

 

 

 

 

 

 

charge correct?

 

 

 

 

Is overload protector normal?

 

 

 

 

 

 

 

 

 

 

 

No,

 

 

 

 

 

 

 

Charge refrigerant

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the abnormality the same

 

 

 

 

 

 

 

 

 

after gas charging?

 

 

 

 

 

Replace the outdoor PCB.

 

 

 

 

 

 

 

 

 

 

 

There is a restriction (Such as capillary or welded points of the pipes.)

No

No

Reconnect and retest

Replace it