Meanwhile, the compressor running frequency is limited by the current.

Frequency decreases

Frequency

holds

If the current increases more than I2HEAT, the frequency will decrease automatically, if the current raises to over I3HEAT,, the compressor will stop and restart 3min later.

During the frequency decreasing, if the current deceases to between I1HEAT, and I3HEAT,, the frequency will hold. If the frequency not does not for 3min, frequency will increase to a higher level, and it can increase twice at most.

If the current deceases to lower than I1HEAT, the frequency limit will be invalid.

Model

 

Current

 

I1HEAT

I2HEAT

I3HEAT

 

VMH09SC-1

5.2

6.4

7.5

VMH12SC-1

5.2

6.4

7.5

VMH18SC-1

5.2

6.4

7.5

VMH24SC-1

10

11

13

8.4.3.2 Outdoor fan running rules:

Outdoor fan and compressor start up at the same time, outdoor fan stops 30s after the compressor stops. The outdoor fan has two speeds, and is controlled by T4 as follows:

T4

°F °C

62(17)

59(15)

27