Heat Controller VMH18SC-1 VMH Series, High evaporator coil temp.T2 protection, Auto-mode

Models: VMH18SC-1 VMH09SC-1 VMH24SC-1 VMH12SC-1

1 45
Download 45 pages 50.02 Kb
Page 31
Image 31
8.4.3.5 High evaporator coil temp.T2 protection:
Running mode
Cooling
Fan-only
Heating

Heat Controller, Inc.

VMH Series

Service Manual

 

 

 

8.4.3.5 High evaporator coil temp.T2 protection:

(1) T2>TEH2 compressor running frequency decreases to the lower level every 20s. If the frequency decreased to F2 and the T2 still over TEH2 for 3 minutes, the compressor will stop. If T2 deceased to lower than 118°F/48°C, or 118°F/48°C <T2< TEH2 last for 6 minutes, release the frequency limit control.

Unit

°F TEH2 (°C)

9K/12K

127°F

53°C

18K /24K

131°F

55°C

(2) If T2>140°F/0°C, the compressor stops and restarts when T2<118°F/48°C

8.4.4 Auto-mode

This mode can be selected by the remote control and the set temperature can be changed between 17~86°F/62°C.

In auto mode, the machine will select cooling, heating or fan-only mode according to the difference between T1 and Ts.

T1-Ts

T1-Ts1°F

-1< T1-Ts ≤1°F

T1-Ts ≤-1°F

Indoor fan will run in auto fan of the relevant mode.

The louver operates the same as in relevant mode.

If the machine switches mode between heating and cooling, the compressor will stop for 15 minutes and then choose mode according to T1-Ts again.

If the set temperature is modified, the unit will choose run function again.

31

Page 31
Image 31
Heat Controller VMH18SC-1, VMH12SC-1, VMH24SC-1, VMH09SC-1 VMH Series, High evaporator coil temp.T2 protection, Auto-mode