6.2 Pipe length and the elevation:

Service Manual

VMH Series

Heat Controller, Inc.

 

 

 

6.2 Pipe length and the elevation:

1.Single Zone “V” Series Inverter System:

Capacity

 

Pipe Size

Standard

 

 

 

Max

Total

 

 

Additional

Btu/h

Gas

Liquid

Length A

 

 

Elevation B

Line Length (ft) A

Refrigerant

 

(in)

(in)

(ft)

 

 

 

(ft)

Min.

 

Max.

oz/ft

9k

3/8

1/4

*16.5

26

10

 

65.5

 

.2

12k

1/2

1/4

*16.5

26

10

 

65.5

 

.2

18k

1/2

1/4

*16.5

32

10

 

82

 

.2

24k

5/8

3/8

*16.5

32

10

 

82

 

.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant Charge (oz)

 

 

 

 

 

 

Unit Model #

 

 

 

 

Heat Pump

 

 

 

 

 

 

VMH09SC

 

 

 

 

38.8 oz.

 

 

 

 

 

 

VMH12SC

 

 

 

 

44.1 oz.

 

 

 

 

 

 

VMH18SC

 

 

 

 

58.2 oz.

 

 

 

 

 

 

VMH24SC

 

 

 

 

67.0 oz.

 

 

 

*Unit charge located on rating plate includes enough refrigerant for 16.5 feet of line set. *Charge adjustment is not required on line set lengths less than 16.5 feet.

*Capacity is based on standard line set lengths and maximum length is based on reliability.

Oil Traps:

It is not necessary to install oil traps when outdoor unit is located lower than indoor unit.

It is recommended that a trap be installed when outdoor unit is installed 16.5’ higher than indoor unit.