Heat Controller, Inc. | VMH Series | Service Manual |
|
|
|
Note:
When
F:Maintains the current frequency.
G:Decreases the frequency to the lower level F1.
H:Runs at F1 for 1h.(if
Frequency decreases
Frequency
holds
If the current increases more than I2COOL, the frequency will decrease automatically, if the current raises to over I3COOL, the compressor will stop and restart 3min later.
When the frequency decreases and the current deceases to between I1COOL and I2COOL, the frequency will hold. If the frequency does not change for 3min, the frequency will increase to a higher level, and it can increase twice at most.
If the current deceases to lower than I1COOL, the frequency limit will be invalid.
Model |
| Current |
| |
I1COOL | I2COOL | I3COOL | ||
| ||||
5.2 | 6.4 | 7.5 | ||
5.2 | 6.4 | 7.5 | ||
5.2 | 6.4 | 7.5 | ||
10 | 11 | 13 |
23