After A/C starts up, the compressor will run at the Fmax frequency for 7 minutes according to outdoor ambient temp. During the 7 minutes, frequency limitation is active.

7 minutes later, compressor running frequency will be controlled as below:

T1-Ts-ΔT

 

°F

°C

41

(+5.0)

40

(+4.5)

38

(+3.5)

37

(+3.0)

37

(+2.5)

36

(+2.0)

35

(+1.5)

34

(+1.0)

33

(+0.5)

 

 

While

Temp. zone

A

B

C

D

E

F

G

Frequency

F10

F9

F8

F7

F5

F3

F4

ΔT=32°F/0°C as default.

Note:

When T1-Ts stays in the same temp. zone for 3 minutes, the compressor will run as follows: A~E: Increase the frequency to the higher level F10.

F:Keeps the current frequency.

G:Decreases the frequency to the lower level F1.

H:Runs at F1 for 1h. (If T1-Ts-ΔT >43°F/6°C, compressor will stop)

26