SECTION 7 − OPERATING AUXILIARY EQUIPMENT
7-1. Standard Receptacles
1 | 6 | 7 | 3 |
|
| ||
| 2 |
| 4 |
|
|
|
5
244
! If unit does not have GFCI recep- tacles, use
.Generator power decreases as weld
current increases.
Set Fine Control R1 at 10 for full gen- erator power.
1 240 V 50 A AC Receptacle RC1
RC1 supplies 60 Hz
2120 V 20 A AC Duplex Receptacle RC2
3120 V 20 A AC Duplex Receptacle RC3
RC2 and RC3 supply 60 Hz
4 240 V 50 A AC Receptacle RC5
RC5 supplies 60 Hz
5 Supplementary Protector CB1
CB1 protects receptacles RC1, RC2, RC3, and RC5 from overload. If CB1 opens, the receptacles do not work. Place switch in On position to reset.
6Supplementary Protector CB2
7Supplementary Protector CB3
CB2 protects RC2 and CB3 protects RC3 from overload. If a supplementary protec- tor opens, the receptacle does not work.
Combined output of all receptacles limited to the rating of the generator.
.Press button to reset. If supplementa-
ry protector continues to open, con- tact Factory Authorized Service Agent.
Example: If 20 A is drawn from each 120 V duplex receptacle, only 26 A is available at the 240V receptacle:
2 x (120 V x 20 A) + (240 V x 26 A) = 11.0 kVA/kW